Weil-McLain Boiler: Check pressure switch sense hoses
Check pressure switch sense hoses on a Weil-McLain boiler: Sense lines must be in good condition and on the correct fittings. Wrong or loose lines cause unreliable operation.
Applies to: Pressure switch sense lines
Common causes of check pressure switch sense hoses
- Hoses swapped or disconnected.
- Cracked or worn plastic reference line.
How to fix check pressure switch sense hoses: step by step
- Check every pressure switch sense hose against Figure 78.
- The blue hose runs from the gas valve to the shroud.
- The black hose runs from the flue pressure switch to the hose barb on the condensate dish.
- Check the plastic gas valve/venturi reference line is attached and in good shape.
- Replace any hose or line that is damaged or misrouted.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: SVF Series 1 boiler manual, p. 87. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.