Weil-McLain Boiler: Wire 0-10VDC remote target input

Updated · by Aurora Star Tech Inc.

Wire 0-10VDC remote target input on a Weil-McLain boiler: The 0-10VDC signal adjusts the supply target temperature and replaces the outdoor sensor as the target modifier.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: ECO Tec Series 3 all models with 0-10VDC modulation

How to fix wire 0-10vdc remote target input: step by step

  1. Connect the 0-10VDC signal to J16 pins 5 (common) and 6 (positive).
  2. Assign a priority to a dry contact heat demand input. A dry contact demand is required to start a call for heat.
  3. Use PRIORITY 1 for indirect DHW (default values are for direct-piped indirect DHW). Use PRIORITY 2 for heating systems, or PRIORITY 2 or 3 on combi.
  4. Set TARGET ADJUST to 0-10V for the priority used.
  5. Set the voltage and temperature points (see the 0-10VDC target settings table).
  6. Between the max and min voltage points, the target temperature changes in proportion.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

Source: ECO Tec series 3 condensing gas boiler boiler manual, p. 72. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.