Weil-McLain Boiler: Sidewall direct vent: locate termination and run vent piping
Sidewall direct vent: locate termination and run vent piping on a Weil-McLain boiler: Plan the sidewall vent and air routing before cutting any holes. Use only the vent and air materials listed in the manual's vent kit figure.
Applies to: SVF 1500-3000 sidewall direct vent (Category IV)
How to fix sidewall direct vent: locate termination and run vent piping: step by step
- Read the vent/air instructions and the manual sections before starting vent work.
- Keep the total vent run from boiler to termination under the maximum length in the vent length figure (page 31, not on these pages).
- Pick a spot that is not exposed to thrown objects, leaves or sediment buildup, and keep it above grade and snow line.
- Route vent and air piping from the boiler connections to the chosen sidewall location.
- Use sweep elbows wherever possible; short-radius elbows cut allowable pipe length.
- Install the vent adapter and reducer at the boiler vent connection if needed.
- Slope horizontal vent piping at least 1/4 inch per foot toward the boiler.
- Support piping independently of the boiler every 5 feet on horizontal and vertical runs, and within 6 inches of any upturn.
- Put a locking collar on every joint of polypropylene vent piping.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: SVF Series 1 boiler manual, p. 41. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.