Weil-McLain Boiler: Chemical cleaning of domestic hot water circuit: precautions
Chemical cleaning of domestic hot water circuit: precautions on a Weil-McLain boiler: Read before any descaling. Water harder than 7 grains must be treated before it enters the combi. Only NSF-approved cleaners safe for consumption and compatible with 316 stainless (brazed plate) and brass (manifolds, temperature sensor) may be used. Keep the boiler water side at 50 psig or less, limited by an approved relief valve. Do not work on sealed control parts.
Applies to: 80/110/150/199 Series 3
Common causes of chemical cleaning of domestic hot water circuit: precautions
- Scale in the DHW circuit reduces hot water output
- Hard or untreated water
How to fix chemical cleaning of domestic hot water circuit: precautions: step by step
- Disconnect the unit from electrical power at the switch or cut-off device before cleaning.
- Follow the chemical manufacturer's dwell time limit, which must be less than the maximum stated on the data sheet.
- Dispose of chemicals and rinse water per current regulations.
- After cleaning, check DHW temperature. The Consumer Product Safety Commission and some states recommend 130°F or less at the tap.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: ECO Tec series 3 boiler manual, p. 154. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.