Weil-McLain Boiler: Gas valve adjustment at low fire (offset)
Gas valve adjustment at low fire (offset) on a Weil-McLain boiler: Only for a qualified technician. Check low fire after high fire has been set.
Applies to: SVF 1500-3000
How to fix gas valve adjustment at low fire (offset): step by step
- Lock the boiler at low fire in Manual Test Mode.
- Confirm the displayed blower rpm matches the low fire value in the table.
- Check CO2 at low fire.
- If low fire is not acceptable, use a 2.5 mm Allen wrench on the offset adjustment.
- Turn toward plus to raise CO2 or toward minus to lower it. Use 1/2 turn, then back off 1/4 turn.
- Re-check high fire, then low fire, and repeat until both meet the CO2 values.
- Return the firing rate to Auto.
- If both cannot be met, contact Weil-McLain.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: SVF Series 1 boiler manual, p. 89. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.