Weil-McLain Boiler: Gas valve adjustment at low fire (offset)

Updated · by Aurora Star Tech Inc.

Gas valve adjustment at low fire (offset) on a Weil-McLain boiler: Only for a qualified technician. Check low fire after high fire has been set.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: SVF 1500-3000

How to fix gas valve adjustment at low fire (offset): step by step

  1. Lock the boiler at low fire in Manual Test Mode.
  2. Confirm the displayed blower rpm matches the low fire value in the table.
  3. Check CO2 at low fire.
  4. If low fire is not acceptable, use a 2.5 mm Allen wrench on the offset adjustment.
  5. Turn toward plus to raise CO2 or toward minus to lower it. Use 1/2 turn, then back off 1/4 turn.
  6. Re-check high fire, then low fire, and repeat until both meet the CO2 values.
  7. Return the firing rate to Auto.
  8. If both cannot be met, contact Weil-McLain.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

Source: SVF Series 1 boiler manual, p. 89. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.