Weil-McLain Boiler: Steam boiler condensate return
Steam boiler condensate return on a Weil-McLain boiler: A steam system needs adequate condensate return to keep a steady water level in the boiler.
Applies to: EG and PEG steam boilers
Common causes of steam boiler condensate return
- Inadequate condensate return to the boiler
- Raw makeup water added to the boiler
How to fix steam boiler condensate return: step by step
- Do not add raw makeup water to the boiler.
- If condensate return is not adequate, install a low water cutoff/pump control, condensate receiver and condensate boiler feed pump.
- Size the condensate equipment per Table 7 (page 24).
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: EG/PEG Series 7 boiler manual, p. 24. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.