Weil-McLain Boiler: Cleaning the CGa temperature/LWCO sensor probe
Cleaning the CGa temperature/LWCO sensor probe on a Weil-McLain boiler: Deposits on the probe affect the water temperature and low water readings. Clean it once a year.
Applies to: CGa-25 to CGa-8, natural gas (config #15) and propane (config #5)
Common causes of cleaning the cga temperature/lwco sensor probe
- Scale or dirt on the probe and insulator
How to fix cleaning the cga temperature/lwco sensor probe: step by step
- Turn off power to the boiler before unplugging connectors or measuring resistance.
- Unplug the harness from the sensor.
- Drain the boiler below the sensor and remove the sensor.
- Wipe the build-up off the probe and the insulator.
- Reinstall with suitable thread sealant. Do not over-tighten.
- Refill, purge air and check for leaks. Then test the LWCO with the LWCO TEST button.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Weil-McLain CGa Series 4 Boiler Manual 550-100-223/0425, Service and maintenance - Temperature/LWCO sensor, p.59. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.