Updated · by Aurora Star Tech Inc.

Boiler shut down or locked out by an external limit on J20 on a Weil-McLain boiler: J20 has two limit circuits, each shipped with a jumper. Pins 1-2 are manual reset: if a limit there opens, the boiler locks out, the alarm contacts close and someone has to reset the control. Pins 3-4 are auto reset: the boiler stops and starts again 150 seconds after the limit closes.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: ECO Tec 80, 110, 150, 199 Series 3 (heat only)

Common causes of boiler shut down or locked out by an external limit on j20

  • External limit contact open
  • Factory jumper missing or loose when no external limit is used
  • Limit wired to the wrong J20 pair

How to fix boiler shut down or locked out by an external limit on j20: step by step

  1. Safety first: turn off power at the service switch before touching wiring. Gas-side work is for a qualified gas technician only.
  2. Check which J20 pair the external limit is wired to (1-2 manual reset, 3-4 auto reset).
  3. Check the limit itself is closed. The contacts must be isolated dry contacts.
  4. If no external limit is used on a pair, its factory jumper must be in place.
  5. Manual-reset pair: the limit has to close first, then reset the control at the display.
  6. Auto-reset pair: after the limit closes, give it 150 seconds to restart on its own.
  7. Remote alarm on J18 terminals 4-5 only closes on a manual lockout (rated 24 VAC or less, 0.5 A or less). It will not signal an auto-reset trip.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

Source: Weil-McLain ECO Tec Series 3 Advanced Manual 550-100-600/1025, sec. Field wiring F. External limits, p.13-14; H. Alarm contacts, p.14. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.