Weil-McLain Boiler: Shadow boiler not showing on the multi-boiler network
Shadow boiler not showing on the multi-boiler network on a Weil-McLain boiler: One ECO Tec master can run up to 8 boilers over RS485. After power-up it can take 30 seconds to 1 minute before the master sees the shadows.
Applies to: ECO Tec 80, 110, 150, 199 Series 3 (heat only)
Common causes of shadow boiler not showing on the multi-boiler network
- Duplicate or missing shadow address
- RS485 wiring wrong or looped back to the master
- Communication harness not installed
How to fix shadow boiler not showing on the multi-boiler network: step by step
- Safety first: turn off power at the service switch before touching wiring. Gas-side work is for a qualified gas technician only.
- Wait 1 minute after power-up before calling it a fault.
- Give each shadow its own address from 2 to 8. No two boilers can share an address.
- The RS485 harness kit (P/N 383700272) plugs into J12.
- Wire master A2/B2/GND to shadow 2 A2/B2/GND, then shadow 2 A3/B3/GND to shadow 3, and so on.
- Do not run the last shadow back to the master's A3/B3/GND. Ground the drain wire at the last boiler.
- With Unity boilers on the network, the ECO Tec must be the master.
- A boiler that drops off and comes back is put back where it was by the master on its own.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Weil-McLain ECO Tec Series 3 Advanced Manual 550-100-600/1025, sec. Multiple boilers / control features, p.4; Multiple boiler communication wiring, p.17-18. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.