Weil-McLain Boiler: Manual reset procedure for ignition lockout

Updated · by Aurora Star Tech Inc.

Manual reset procedure for ignition lockout on a Weil-McLain boiler: Use this procedure to clear a manual reset lockout caused by an ignition fault.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: EG and PEG Series 7 water boilers

How to fix manual reset procedure for ignition lockout: step by step

  1. Make sure the ignition fault has been corrected first.
  2. On the fault indication screen, press and release the enter button to open the confirmation screen.
  3. The reset question shows NO on line 2. Press enter to change it.
  4. Press the up or down arrow to change the answer to YES, then press enter again.
  5. The display background turns green and returns to the main screen.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

More reset & cancel tips for boiler

Source: EG / PEG Series 7 Boiler Manual, p. 74. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.