Weil-McLain Boiler: Popping or percolating noise in boiler
Popping or percolating noise in boiler on a Weil-McLain boiler: Noise from mineral scale in sections, often from constant makeup water or wrong water pH.
Applies to: All listed CGa, CGi, EG, PEG and LGB boilers
Common causes of popping or percolating noise in boiler
- Mineral deposits in sections from constant makeup water
- Incorrect boiler water pH
- Insufficient water flow through boiler
How to fix popping or percolating noise in boiler: step by step
- Have a qualified service technician de-lime the boiler if necessary; very heavy deposits may not come off by de-liming
- Have a qualified service technician repair leaks so makeup water is no longer needed
- Have a qualified service technician check and correct pH; keep it between 7.0 and 8.5
- Check all valves to and from the boiler and return them to the proper setting
- Confirm the circulator is correctly sized
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Weil-McLain CGa, CGi, EG, PEG & LGB user manual, p. 9. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.