Weil-McLain Boiler: Replacing a boiler on an existing common vent
Replacing a boiler on an existing common vent on a Weil-McLain boiler: The Ultra cannot share a common vent with any other appliance. The old vent may be oversized for the appliances that remain on it, so test them before finishing the job.
Applies to: Any Ultra boiler replacing a boiler on a shared chimney or common vent
Common causes of replacing a boiler on an existing common vent
- Old vent sized for the removed boiler plus remaining appliances
- Vent may be too large for the remaining appliances once the old boiler is removed
How to fix replacing a boiler on an existing common vent: step by step
- Inspect the existing vent for correct size, horizontal pitch, blockage, leakage, corrosion or other defects.
- Close building doors and windows and doors to other spaces. Run clothes dryers, non-vented appliances and exhaust fans (range hoods, bath fans) at full speed. Do not run a summer exhaust fan. Close fireplace dampers.
- Run each remaining appliance alone with the others off. Set its thermostat so it runs continuously.
- After 5 minutes of main burner operation, check the draft hood relief opening for spillage with a flame, candle or smoke.
- Return doors, windows, fans and dampers to normal. If the vent fails, correct it to the National Fuel Gas Code (ANSI Z223.1 or B149.1/B149.2 in Canada), typically by resizing toward the minimum size from the code tables.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Weil-McLain Ultra Series 4 boiler manual, p. 16. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.