Weil-McLain Boiler: No outdoor sensor installed
No outdoor sensor installed on a Weil-McLain boiler: The outdoor sensor ships with the boiler and is required unless the job meets one of the exemptions. Without it, two settings must be changed.
Applies to: ECO Tec 80, 110, 150, 199 Series 3 (heat only)
Common causes of no outdoor sensor installed
- Sensor not installed on an exempt job
- Sensor left off on a job that is not exempt
How to fix no outdoor sensor installed: step by step
- Exemptions: an energy management system lowers boiler water temperature as load drops, the boiler does no space heating, or it is part of a multi-boiler system of 300,000 BTU/h total or more.
- Without the sensor, set Target Adjust in each priority to NONE (fixed supply temperature) or 0-10V (remote target).
- Set WWSD to OFF.
- Set Outdoor Temp Sensor Exempt to YES only if the job really is exempt.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Weil-McLain ECO Tec Series 3 Advanced Manual 550-100-600/1025, Outdoor sensor exemption notice, p.2; Boiler Settings, p.58. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.