Weil-McLain Boiler: Six-month relief valve operation test

Updated · by Aurora Star Tech Inc.

Six-month relief valve operation test on a Weil-McLain boiler: Lift the relief valve lever to check that it flows and reseats without weeping. Pipe the discharge to a safe place before testing.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Ultra Series 4 boiler relief valve and discharge line

Common causes of six-month relief valve operation test

  • Valve weeps after being lifted
  • Valve or discharge line blocked
  • Valve seat dirty

How to fix six-month relief valve operation test: step by step

  1. Verify the relief valve outlet is piped to a safe discharge location that avoids scalding.
  2. Confirm the discharge line is metal and runs to a safe disposal point, as installed per the Ultra boiler manual.
  3. Read the pressure/temperature gauge to confirm the system is pressurized.
  4. Lift the relief valve top lever slightly so water flows through the valve and discharge piping.
  5. If water flows freely, release the lever and let the valve seat.
  6. Watch the discharge pipe end after it drains. If the valve weeps, lift the lever again to clean the seat.
  7. If the valve still weeps, call a qualified service technician to inspect the valve and system.
  8. If no water flows when the lever is fully lifted, shut the boiler down following page 9 and call a qualified service technician to check for a blocked valve or discharge line.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

Source: Ultra Series 4 user's information manual, p. 8. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.