Weil-McLain Boiler: Adjust boiler bypass valves (high water content systems)
Adjust boiler bypass valves (high water content systems) on a Weil-McLain boiler: For high water content systems such as converted gravity systems. Not for radiant panel systems. Does not protect against high supply temperature.
Applies to: Boiler bypass method, Figure 20. Do not use on radiant panel systems.
Common causes of adjust boiler bypass valves (high water content systems)
- Low water temperature in the boiler, causing corrosion of sections or burners
How to fix adjust boiler bypass valves (high water content systems): step by step
- Start with valve 1 fully closed and valve 2 fully open.
- Slowly open valve 1 while closing valve 2.
- Adjust until the boiler gauge reads about 60°F higher than the system temperature gauge.
- Pause between adjustments so temperatures can level off.
- Install all components specified and adjust valves so the boiler never runs at low temperature.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: EG/PEG Series 7 boiler manual, p. 23. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.