Weil-McLain Boiler: 0-10VDC remote modulation input setup and operation
0-10VDC remote modulation input setup and operation on a Weil-McLain boiler: Remote modulation works only on a single boiler, not one in a network. It replaces the INPUT 1 heat demand, and the control cannot use both 0-10VDC target and modulation.
Applies to: Single boiler remote modulation
How to fix 0-10vdc remote modulation input setup and operation: step by step
- Set up the boiler as a single boiler in the Unity control.
- Connect the signal positive to terminal 6 and common to terminal 5 on P15.
- Assign INPUT 1 to PRIORITY 2 during the WIZARD.
- In the ASSIGN INPUTS menu for INPUT 1, change SOURCE from TT1 to 0-10V.
- Expect a heat demand at 0.9 VDC, which turns off at 0.8 VDC.
- 2 VDC equals 10% input and 10 VDC equals 100% input. These voltage points are fixed.
- OUTPUT 1 energizes with the heat demand and can drive the system pump.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
More settings shortcuts tips for boiler
Source: SVF Series 1 boiler manual, p. 64. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.