Weil-McLain Boiler: Expansion tank and make-up water piping

Updated · by Aurora Star Tech Inc.

Expansion tank and make-up water piping on a Weil-McLain boiler: Size the expansion tank for the boiler and system water volume and temperature (boiler water content on page 120). An undersized tank lets water blow out of the relief valve and add make-up water through the fill valve, which can eventually fail the boiler. Connect the tank to the air separator only if the separator is on the pump suction side. Install the system fill connection at the same point as the expansion tank connection. With a diaphragm or bladder tank, put an automatic air vent on top of the air separator, and where the boiler sits above main piping, put one in the outgoing boiler piping. Pre-charge diaphragm tanks to the system fill pressure before connecting. With a closed-type tank, do not install automatic air vents, pitch horizontal piping up toward the tank 1 inch per 5 feet, and use at least 3/4 inch piping to the tank.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: All SVF 1500-3000 system piping

Common causes of expansion tank and make-up water piping

  • Undersized expansion tank
  • Automatic air vent installed on a closed-type tank
  • Fill point not at the same point as the tank connection

How to fix expansion tank and make-up water piping: step by step

  1. Confirm the tank volume handles boiler and system water volume and temperature (see page 120).
  2. Connect the tank to the air separator only if the separator is on the pump suction side.
  3. Put the system fill connection at the same point as the expansion tank connection.
  4. For a diaphragm tank, pre-charge it to fill pressure and fit an automatic air vent on the air separator.
  5. For a closed-type tank, skip automatic air vents, pitch horizontal piping up 1 inch per 5 feet toward the tank, and use at least 3/4 inch piping.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

Source: SVF 1500-3000 Series 1 boiler manual, p. 16. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.