Weil-McLain Boiler: Check inhibitor and antifreeze levels yearly
Check inhibitor and antifreeze levels yearly on a Weil-McLain boiler: Water chemistry and antifreeze strength change over time, so test them at least once a year.
Applies to: Systems with inhibitor or antifreeze
Common causes of check inhibitor and antifreeze levels yearly
- Inhibitor level drops over time.
- Antifreeze concentration drops if a fitting or seal leaks and only water is lost.
How to fix check inhibitor and antifreeze levels yearly: step by step
- Test the pH of a system water sample. It must be between 7.0 and 8.5.
- Use the Sentinel inhibitor test kit to check inhibitor concentration.
- If pH is out of range or the inhibitor is low, add inhibitor or treat the system as the manual directs.
- Test antifreeze concentration. If it is low, add antifreeze or drain and refill with the correct mix.
- Recheck inhibitor level after any adjustments.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: SVF Series 1 boiler manual, p. 86. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.