Weil-McLain Boiler: Direct exhaust conversion and combustion air openings
Direct exhaust conversion and combustion air openings on a Weil-McLain boiler: Direct exhaust conversion requires the Weil-McLain Direct Exhaust Venting Kit. Boiler room combustion air openings must be sized for all appliances in the room, including the ECO Tec BTU rating. Openings are sized per the manual figure. Negative pressure from exhaust fans or other mechanical ventilation can defeat the openings.
Applies to: Direct exhaust option, all 80/110/150/199
Common causes of direct exhaust conversion and combustion air openings
- Boiler room under negative pressure from exhaust fans or mechanical ventilation
- Other appliances in the room not counted in air sizing
How to fix direct exhaust conversion and combustion air openings: step by step
- Use the Direct Exhaust Venting Kit to convert the boiler to direct exhaust.
- Follow both this manual and the Direct Exhaust Venting Kit instructions.
- Install 3 in PVC or CPVC pipe and elbow on the boiler air inlet and a 3 in screen in the elbow opening.
- Use the template to cut only the exhaust hole in the wall.
- Add the ECO Tec BTU rating to the room total with all other appliances when sizing air openings.
- Check that the room is not under negative pressure.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: ECO Tec Series 3 Boiler Manual, p. 45. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.