Weil-McLain Boiler: Thermostat, DHW sensor and anticipator wiring
Thermostat, DHW sensor and anticipator wiring on a Weil-McLain boiler: Default input terminals and wiring precautions for thermostats and DHW tank control.
Applies to: Ultra U-Control heat demand inputs
How to fix thermostat, dhw sensor and anticipator wiring: step by step
- For default operation, connect the space heating thermostat to terminal strip P15, terminals 1 and 2.
- For default DHW operation, connect the DHW tank temperature control across terminal strip P11, terminals 4 and 5.
- Install thermostats on inside walls away from drafts, water pipes, lights, TV, sun and fireplaces.
- If the thermostat connects directly to the boiler, set its anticipator to 0.1 A.
- If it connects to relays or other devices, set the anticipator to match the total power draw of those devices.
- Use isolating relays with 3-wire zone valves to prevent stray voltage damage and nuisance problems.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Weil-McLain Ultra Series 4 boiler manual, p. 95. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.