Updated · by Aurora Star Tech Inc.

Set up 0-10VDC remote target input on a Weil-McLain boiler: A 0-10VDC signal adjusts the supply target temperature through the TARGET ADJUST setting. The control interpolates the target between the set voltage and temperature points.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Remote target input in PRIORITY SETTINGS

How to fix set up 0-10vdc remote target input: step by step

  1. Use PRIORITY 1 for DHW if used, and verify its settings.
  2. Use PRIORITY 2 for heating and set TARGET ADJUST to 0-10V.
  3. Set VOLTS FOR MAX to the voltage that calls for the highest target, and set SUPPLY MAX to that temperature.
  4. Set VOLTS FOR MIN to the voltage that calls for the lowest target, and set SUPPLY MIN to that temperature.
  5. Connect the signal positive to P15 terminal 6 and common to terminal 5.
  6. A dry contact heat demand must still be wired to an input to start a call for heat.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

More settings shortcuts tips for boiler

Source: SVF Series 1 boiler manual, p. 63. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.