Weil-McLain Boiler: Additional heat demand (AHD) behaviour
Additional heat demand (AHD) behaviour on a Weil-McLain boiler: AHD can be set to 1st, 2nd or Outdoor Temperature. With 1st, the contact closes at once on a call and the boiler starts only if the call is still active when RESPONSE TIME expires and the system is below target minus system-on differential. With 2nd, the boiler starts immediately and the AHD contact closes after RESPONSE TIME. TEMP DEPENDENT = YES requires system supply below target before the AHD contact and 0-10V output act; this needs a valid supply and return sensor pair. The outdoor setpoint option needs a valid outdoor sensor. A master boiler cannot use AHD on a local priority; network AHD must be wired to the master.
Applies to: ECO Tec Series 3 priority menus
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: ECO Tec Series 3 boiler manual, p. 122. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.