Weil-McLain Boiler: Water piping and recommended pipe sizing
Water piping and recommended pipe sizing on a Weil-McLain boiler: The boiler has 3 inch Class 150 flanged connections, so use reducers to adapt to the external piping. Use two wrenches when tightening water piping at the boiler, holding the internal piping so it does not turn. Size the pumps and piping for the required temperature rise using the head loss curve (Figure 9) and flow table (Figure 10). Size system piping per Figure 11. For glycol mixes the temperature rise will differ, but flow must stay within range. Flows outside the Figure 10 range need primary/secondary piping, a differential bypass valve in variable primary systems for high flow, or a flow switch set at minimum flow for low flow. Insufficient flow causes limit nuisance outages; excess flow can erode the heat exchanger.
Applies to: All SVF 1500-3000 models
How to fix water piping and recommended pipe sizing: step by step
- Fit reducers from the 3 inch Class 150 flanges to the external piping.
- Hold the boiler internal piping with one wrench while tightening with the other.
- Select pipe size and pump for the desired temperature rise, using Figure 10 and Figure 11.
- For flows outside the Figure 10 range, use primary/secondary piping or a bypass valve (high flow) or a flow switch at minimum flow (low flow) in a variable primary system.
- For glycol systems, confirm flow stays in range and get the temperature rise from the glycol supplier.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: SVF 1500-3000 Series 1 boiler manual, p. 14-16. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.