Weil-McLain Boiler: Test probe-type low water cutoff
Test probe-type low water cutoff on a Weil-McLain boiler: Checks that the probe-type low water cutoff stops firing at low water and allows firing once refilled.
Applies to: EG and PEG steam boilers with probe-type LWCO
How to fix test probe-type low water cutoff: step by step
- Turn off power to the boiler and wait 5 minutes.
- Drain water to the bottom of the gauge glass.
- Turn on power.
- Set the thermostat to call for heat. The red neon lamp on the lower water cutoff should light.
- Wait 5 minutes. The boiler should not fire.
- Refill the boiler to the correct waterline. The red lamp should go off.
- Wait 5 minutes. The boiler should fire.
- Return the thermostat to its normal setting.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Weil-McLain EG/PEG Series 7 Boiler Manual, p. 70. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.