Weil-McLain Boiler: Key components and their functions (quick reference)
Key components and their functions (quick reference) on a Weil-McLain boiler: Blower pulls air and gas through the venturi and pushes the mix into the premix burner; the air inlet silencer keeps it quiet. The swirl plate/shroud creates a vacuum the gas valve senses to meter gas. The automatic gas valve gives gas flow proportional to air flow. The expansion module drives the gas valve, monitors gas pressure switches and gives a dry contact for the circulator (up to 10 A). The high and low gas pressure switches and the air pressure switch (max flue pressure) protect the combustion system. The low water cutoff sits on the outlet pipe and resets through the main control. The ignition electrode sparks to light the burner, and the flame sense rod reads the flame signal. Outlet, inlet and flue temperature sensors feed the control. The display and buttons set up the boiler, change display mode and reset after lockout.
Applies to: SVF 1500-3000 Series 1
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: SVF Series 1 Boiler Manual, p. 2-3. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.