Weil-McLain Boiler: Install the Weil-McLain sidewall vent/air cap
Install the Weil-McLain sidewall vent/air cap on a Weil-McLain boiler: Mark, cut and mount the outside and inside wall plates first, then fit the termination, then run piping to the boiler.
Applies to: Ultra boilers using the Weil-McLain sidewall termination plate
How to fix install the weil-mclain sidewall vent/air cap: step by step
- Set the template supplied with the kit on the outside wall. Level it with a spirit level so the vent and air openings sit side by side.
- Mark the four mounting holes, the vent opening and the air opening. Check for obstructions first.
- Cut the wall openings. Drill small centering holes first, then drill the large openings from both inside and outside. A single rectangular cutout may replace two holes.
- Drill the outside plate holes, install the outside plate and temporarily mount the termination.
- Cut the vent pipe so it fully enters the termination socket. Cut the air pipe so it butts against the stops inside the termination.
- On Ultra-230 installs using 3-inch vent pipe with a 4-inch termination, enlarge the vent pipe to 4 inch before it passes through the wall.
- Slide the pipes through the opening and position the inside plate so the pipes slope down toward the boiler at 1/4 inch per foot. Mark, remove the pipes, drill and mount the inside plate.
- Test fit the termination. Apply silicone RTV sealant inside the vent termination, slide it onto the vent pipe and rotate slightly to spread the sealant.
- Secure the termination with four #10 x 1/2 inch sheet metal screws and lock washers.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Ultra Series 4 boiler manual, p. 70. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.