Updated · by Aurora Star Tech Inc.

Vertical direct vent: roof vent and air terminations on a Weil-McLain boiler: Terminate vent and air through the roof or with a sidewall air inlet.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: SVF 1500-3000 vertical direct vent (Category IV)

How to fix vertical direct vent: roof vent and air terminations: step by step

  1. Keep the total outside vent and air piping within the maximum lengths in the manual's termination figure (page 44).
  2. Use sweep elbows for all vent piping where possible.
  3. Slope vent piping at least 1/4 inch per foot toward the boiler.
  4. Support piping independently of the boiler every 5 feet, and within 6 inches of any upturn.
  5. Cut the air pipe hole to the vent/air pipe maker's size.
  6. Cut the vent pipe hole at least 3/8 in larger for combustible construction, or per the vent maker for noncombustible construction.
  7. Insert a corrosion-resistant metal thimble in the vent pipe hole and isolate the pipe per local codes.
  8. Use flashing and sealing boots sized for the vent pipe.
  9. Use a coupling or open-end termination per the vent maker's vertical termination guidelines.
  10. Install a bird screen in the open ends of the terminations.
  11. Keep the finished termination dimensions shown in the manual's figure.
  12. Seal all exterior openings with caulk.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

Source: SVF Series 1 boiler manual, p. 43-44. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.