Weil-McLain Boiler: Check thermostat circuits for stray voltage
Check thermostat circuits for stray voltage on a Weil-McLain boiler: Confirm no voltage is fed back into the control from external devices.
Applies to: ECO Tec Series 3 80/110/150/199
Common causes of check thermostat circuits for stray voltage
- External thermostat, relay or zone valve wired so it puts voltage on the boiler input terminals
How to fix check thermostat circuits for stray voltage: step by step
- Mark and disconnect the wires on Input 1, Input 2, Input 3 and Input 4.
- Close each external thermostat, zone valve or relay one at a time.
- Measure voltage from each wire to ground with a voltmeter. There should never be a reading when the external device is closed.
- If voltage is present, correct the external wiring.
- Do not connect the thermostat terminals to 3-wire zone valves.
- Reconnect the wires once the circuit is correct.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: ECO Tec Series 3 Condensing Gas Boiler Boiler Manual, p. 132. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.