Weil-McLain Boiler: Lockout on the manual reset high temperature limit
Lockout on the manual reset high temperature limit on a Weil-McLain boiler: If boiler outlet water goes over the Manual Reset High Temp Limit setting (200°F from the factory), the control shuts the boiler down and locks out. It needs a manual reset. Weil-McLain does not recommend changing this setting.
Applies to: ECO Tec 80, 110, 150, 199 Series 3 (heat only)
Common causes of lockout on the manual reset high temperature limit
- Boiler outlet water went over the limit setting
- Limit setting was lowered from the 200°F default
How to fix lockout on the manual reset high temperature limit: step by step
- Check the setting: contractor menu > Boiler Settings > Manual Reset High Temp Limit.
- Look at Boiler Out / Boiler In and Target Temp on the boiler information screen.
- Check the target temperatures of each priority. System presets top out at 180°F max target (120°F for slab on grade).
- If the system mixes low-temperature circuits (radiant slab) with high-temperature ones, those low circuits need their own limit wired to an external limit input.
- Reset at the display. If it keeps tripping, go to the ECO Tec Boiler Manual troubleshooting section.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Weil-McLain ECO Tec Series 3 Advanced Manual 550-100-600/1025, sec. Wizard screen, p.29; Boiler Settings, p.58; Figure 25 System Type Presets, p.54; Temperature settings note, p.2. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.