Weil-McLain Boiler: Expansion tank installation
Expansion tank installation on a Weil-McLain boiler: Expansion tank sizing and location must keep the system from losing water through the relief valve.
Applies to: Heating system expansion tank
Common causes of expansion tank installation
- Undersized tank lets water blow out the relief valve and makeup water feed in through the fill valve.
- Leaks in the tank piping let air escape and waterlog the tank.
How to fix expansion tank installation: step by step
- Size the tank for boiler and system water volume and temperature.
- Locate the cold water fill connection at the expansion tank, never elsewhere.
- Install an automatic air vent on top of the air separator for diaphragm or bladder tanks only.
- Do not use an automatic air vent with a closed-type tank.
- Do not use a closed-type tank if connecting to a water heater that has an automatic air vent.
- Slope horizontal piping at least 1 inch per 5 feet.
- Use a tank fitting such as a B&G Tank-trol or Taco-trol on closed-type tanks.
- Correct all leaks in the system or tank piping.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: ECO Tec Series 3 boiler manual, p. 54, 55. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.