Weil-McLain Boiler: No display and blower running at full speed
No display and blower running at full speed on a Weil-McLain boiler: Control is not getting 24 V power.
Applies to: Ultra 80, 105, 155, 230, 299, 399
Common causes of no display and blower running at full speed
- Short circuit or incorrect wiring
- Blown 3 A low voltage fuse
- Transformer wiring wrong or transformer not outputting 24 VAC
How to fix no display and blower running at full speed: step by step
- Check wiring for shorts or errors; correct it to the wiring diagram, including the transformer connection to the U-Control.
- Check the 3 A low voltage fuse (page 116) and replace it with the proper part if blown. If it blows again, recheck wiring.
- Check transformer output. If it receives 120 VAC but gives no 24 VAC, replace the transformer.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Ultra Series 4 gas-fired water boiler manual, p. 118. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.