Weil-McLain Boiler: Flow switch or combustion air damper interlock
Flow switch or combustion air damper interlock on a Weil-McLain boiler: Proof of closure can be a flow switch or a CAD interlock. Both are wired through the J18 jumper location.
Applies to: Evergreen 110/155/220/299/300/399
How to fix flow switch or combustion air damper interlock: step by step
- Remove the jumper on J18 and wire the flow switch or CAD contacts in place of it, as shown in the wiring diagram.
- For a flow switch, no control settings are needed.
- For a CAD interlock, assign Input 3 as an AUX PUMP/OUTPUT, and select local or System Damper for the operating mode.
- Confirm the damper will open whenever the boiler is called to fire. Output 3 supplies 120VAC to the damper motor. Use an isolation relay for a different voltage or for loads above 2.0 A.
- On multi-boiler CAD interlocks, wire all proof of closure inputs in series with the end devices and each boiler's closure switch input.
- Use only electrically isolated contacts, since the J18 jumper circuit carries 5 VDC.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Weil-McLain Series 2 Condensing Gas Boiler Advanced Manual, p. 52. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.