Weil-McLain Boiler: Additional limit controls and external limit wiring

Updated · by Aurora Star Tech Inc.

Additional limit controls and external limit wiring on a Weil-McLain boiler: ASME installations may need a manual reset high temperature limit in the supply piping. Systems with low-temperature circuits should protect them with external limits wired to the Unity-CI control P4 terminals.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: EG / PEG Series 7 water boilers

How to fix additional limit controls and external limit wiring: step by step

  1. If ASME applies, install a manual reset high temperature limit in the system supply piping between the boiler and its isolation valve. Set it to no more than 240°F.
  2. Note that the Unity-CI operating limit shuts the boiler down at 210°F or lower, depending on the set value.
  3. For a manual reset external limit, wire series isolated contacts to P4 terminal 1 by cutting and splicing at mark ‹1›.
  4. For an automatic reset external limit, wire series isolated contacts to P4 terminal 3 by cutting and splicing at mark ‹2›.
  5. If a manual reset limit is used, set the Unity-CI boiler limit at least 20°F below the external manual reset limit (for example, no higher than 180°F for a 200°F external limit).
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

Source: EG / PEG Series 7 boiler manual, p. 33. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.