Weil-McLain Boiler: Altitude derate for input rate
Altitude derate for input rate on a Weil-McLain boiler: In the USA, input is derated 4% for each 1000 ft above sea level beyond 2000 ft. In Canada, input is derated 10% for 2000 to 4500 ft. Use the high altitude fan speed settings. Above 4500 ft in Canada, follow provincial authorities. Above 10,000 ft contact Weil-McLain.
Applies to: SVF 1500-3000
How to fix altitude derate for input rate: step by step
- Check the elevation of the install.
- Apply the derate rule for the country.
- Use the high altitude rpm column from the blower speed tables.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
More commissioning tips for boiler
Source: SVF Series 1 boiler manual, p. 88. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.