Weil-McLain Boiler: Motorized combustion air damper interlock
Motorized combustion air damper interlock on a Weil-McLain boiler: If combustion air openings use motorized dampers, the boiler must not fire unless the damper is proven open.
Applies to: Direct exhaust combustion air openings with motorized dampers
How to fix motorized combustion air damper interlock: step by step
- Wire an isolated contact that proves the damper open in series with the thermostat input to the boiler.
- Confirm the boiler will not start with the contact open.
- Confirm the boiler shuts down if the damper closes during operation.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Ultra Series 4 boiler manual, p. 84. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.