Weil-McLain Boiler: Adjust high fire CO2 at the gas valve throttle screw

Updated · by Aurora Star Tech Inc.

Adjust high fire CO2 at the gas valve throttle screw on a Weil-McLain boiler: Set the high fire CO2 to the target in the combustion table using the throttle screw.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: ECO Tec Series 3 gas boilers

How to fix adjust high fire co2 at the gas valve throttle screw: step by step

  1. Run the boiler at high fire and let it stabilize.
  2. Read CO2 with the combustion analyzer.
  3. If CO2 is high, turn the throttle screw (2.5mm Allen) clockwise in small moves to lower the input.
  4. If CO2 is low, turn the throttle screw counterclockwise to raise the input.
  5. Let the boiler stabilize and read again after each move. Repeat until the target CO2 is reached.
  6. Confirm CO is within limits.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

Source: ECO Tec series 3 boiler manual, p. 136. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.