Weil-McLain Boiler: Choose direct connect or primary/secondary piping

Updated · by Aurora Star Tech Inc.

Choose direct connect or primary/secondary piping on a Weil-McLain boiler: Primary/secondary is recommended and gives the most accurate system temperature. Direct connect is only for eligible heat-only systems.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Heating system piping

How to fix choose direct connect or primary/secondary piping: step by step

  1. Check the system against the direct connect criteria first.
  2. Use primary/secondary piping if the system is ineligible or flow through the heat exchanger would be above the maximum.
  3. Place primary/secondary connection tees no more than 12 inches apart.
  4. Use a bypass pressure regulator on any system zoned with zone valves, unless a modulating circulator with dead-head protection is used.
  5. Do not replace the boiler circulator with anything other than the Taco 0015e3.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

Source: ECO Tec Series 3 boiler manual, p. 53, 54, 56. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.