Updated · by Aurora Star Tech Inc.

Float type low water cutoff: clean and test on a Weil-McLain boiler: Periodic cleaning and function test of a float type low water cutoff. Boiler pressure and temperature must be low first.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Float type low water cutoff

How to fix float type low water cutoff: clean and test: step by step

  1. Make sure the boiler is cool and pressure is low to avoid burns.
  2. Open the blowdown valve at the bottom control and drain into a bucket to flush sediment from the float chamber.
  3. Turn the operating control to call for heat before the water gets hot.
  4. Drain water until the level drops to the bottom of the gauge glass; the boiler should shut off after the level drops a few inches.
  5. Refill to the correct waterline; the boiler should start again.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

Source: Gas-Fired Boilers User Manual 550-100-226/0425, p. 20. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.