Weil-McLain Boiler: Check heat exchanger, vent seals and condensate dish joint
Check heat exchanger, vent seals and condensate dish joint on a Weil-McLain boiler: Check for leaks at high fire using an inspection mirror.
Applies to: ECO Tec Series 3 80/110/150/199
Common causes of check heat exchanger, vent seals and condensate dish joint
- Loose retaining screws or nuts
- Damaged gasket
How to fix check heat exchanger, vent seals and condensate dish joint: step by step
- Operate the boiler on HIGH fire.
- Move an inspection mirror around all heat exchanger joints, vent pipe connections at the top, and the condensate dish joints.
- A leak shows as vapor on the mirror or signs of weepage.
- If a leak is found, shut the boiler down immediately.
- Tighten retaining screws or nuts without over-tightening.
- If the leak continues, disassemble the joint, inspect gaskets and replace any damaged gasket.
- Contact WM Technologies Technical Services if the problem is not solved.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: ECO Tec Series 3 Condensing Gas Boiler Boiler Manual, p. 136. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.