Weil-McLain Boiler: Adjust system bypass valves (primary/secondary bypass)

Updated · by Aurora Star Tech Inc.

Adjust system bypass valves (primary/secondary bypass) on a Weil-McLain boiler: Used for high water content, radiant or low-return-temperature systems. Adjust valves to raise return water temperature to the boiler.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: System bypass method, Figure 19

Common causes of adjust system bypass valves (primary/secondary bypass)

  • Low return water temperature causing flue gas condensation and corrosion

How to fix adjust system bypass valves (primary/secondary bypass): step by step

  1. Start with valve 2 fully closed and valve 1 fully open.
  2. Slowly open valve 2 while closing valve 1.
  3. Adjust both valves until the boiler pressure/temperature gauge reads 160°F or higher.
  4. Pause between adjustments so temperatures can level off, since boiler water temperature rises slowly as flow changes.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

Source: EG/PEG Series 7 boiler manual, p. 22. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.