Weil-McLain Boiler: Adjust system bypass valves (primary/secondary bypass)
Adjust system bypass valves (primary/secondary bypass) on a Weil-McLain boiler: Used for high water content, radiant or low-return-temperature systems. Adjust valves to raise return water temperature to the boiler.
Applies to: System bypass method, Figure 19
Common causes of adjust system bypass valves (primary/secondary bypass)
- Low return water temperature causing flue gas condensation and corrosion
How to fix adjust system bypass valves (primary/secondary bypass): step by step
- Start with valve 2 fully closed and valve 1 fully open.
- Slowly open valve 2 while closing valve 1.
- Adjust both valves until the boiler pressure/temperature gauge reads 160°F or higher.
- Pause between adjustments so temperatures can level off, since boiler water temperature rises slowly as flow changes.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: EG/PEG Series 7 boiler manual, p. 22. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.