Weil-McLain Error Code TEMP RISE TOO QUICKLY: Supply water temperature rising too fast (Boiler)

Updated · by Aurora Star Tech Inc.

Weil-McLain error code TEMP RISE TOO QUICKLY on a boiler means: Supply water temperature rising too fast. It is also called Weil-McLain diagnostic code TEMP RISE TOO QUICKLY.

High severityBoilerECO Tec series 3

Homeowner? What Weil-McLain code TEMP RISE TOO QUICKLY means for you

Call a technician Your boiler is reporting: Supply water temperature rising too fast. The boiler has locked out or cannot run properly. One reset is fine; if the code comes back, it needs a licensed technician to find the cause.

Safe things you can check yourself

  • Check the thermostat: right mode (Heat or Cool), set a few degrees past room temperature, and fresh batteries if it uses them.
  • Make sure the unit has power: its on/off switch (often looks like a light switch near the unit) is ON and the breaker in the electrical panel is not tripped.
  • Look at the pressure gauge on the boiler. If it reads much lower than usual or near zero, or water is leaking, call a technician.
  • Outside, make sure the intake and exhaust pipes or vent cap are not blocked by snow, ice, leaves or a nest.
  • Check that the boiler gas valve is open (handle in line with the pipe).
  • Try one reset: turn the power off for 30 seconds, then back on. If the code comes back, stop resetting and call a technician.

Call (647) 657-2977Book a service call

Licensed technicians serving Vaughan, Toronto and the GTA.

What does Weil-McLain error code TEMP RISE TOO QUICKLY mean?

Occurs if supply water in the heat exchanger rises faster than 10F per second for two seconds during the first two minutes of burner operation. Resets automatically after a one minute delay or by manual reset on the display. After 5 automatic resets during the same priority heat demand, a manual reset is required.

Applies to: ECO Tec series 3 80/110/150/199

Common causes of Weil-McLain code TEMP RISE TOO QUICKLY

  • Water piping not installed per manual
  • Circulator wrong for boiler size or system
  • Loose temperature sensor connection
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

Other Weil-McLain Boiler codes

CodeMeaning
System Return > SupplySystem return hotter than system supply
Target Reduced - BoilerTarget reduced because boiler outlet is near max temperature
Target Reduced - FlowTarget reduced for low water flow across heat exchanger
Target Reduced - FlueTarget reduced for high flue temperature
TEMPERATURE SENSORTemperature sensor short, open, or readings disagree
TEMPERATURE SENSOR FAULTTemperature sensor shorted or open
Unconfigured Net 1 or Net 2 DemandNet 1 or Net 2 input active but not configured
Virtual Input ActiveModbus commanding a virtual TT input

All Weil-McLain Boiler error codes →

Weil-McLain code TEMP RISE TOO QUICKLY: homeowner questions

What does Weil-McLain code TEMP RISE TOO QUICKLY mean?

Supply water temperature rising too fast. Occurs if supply water in the heat exchanger rises faster than 10F per second for two seconds during the first two minutes of burner operation. Resets automatically after a one minute delay or by manual reset on the display. After 5…

Is it safe to keep using my boiler with code TEMP RISE TOO QUICKLY?

It depends on the cause. The boiler has locked out or cannot run properly. One reset is fine; if the code comes back, it needs a licensed technician to find the cause.

Can I reset Weil-McLain code TEMP RISE TOO QUICKLY myself?

You can try one reset (power off for 30 seconds, then on). If Weil-McLain code TEMP RISE TOO QUICKLY comes back, the cause is still there and a licensed technician should check it.

Who can fix Weil-McLain code TEMP RISE TOO QUICKLY near me?

Aurora Star Tech Inc. repairs Weil-McLain boilers in Vaughan, Toronto and across the GTA. Call (647) 657-2977 or book a service call online.

Homeowner help: Boiler Not Heating: What to Check

Troubleshooting guides

Source: ECO Tec Series 3 boiler manual, p. 168. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.