Rheem Error Codes & Diagnostic Codes

Updated · by Aurora Star Tech Inc.

Rheem error codes and diagnostic codes: look up a code to see what it means, the likely causes and the steps to fix it.

Rheem error codes by equipment type

Rheem Furnace error codes

CodeMeaning
0Standby - no call, no fault
1 blinkSoft lockout (failed ignition)
2 blinksPressure switch circuit open
2 WK HIST / LIFE HIST menusFurnace user menus - run-time histories
3 blinksLimit circuit open
4 blinksPressure switch circuit closed (stuck closed)
5 blinksTwinning fault (optional)
6 blinksLine and neutral reversed
10One-hour lockout
11Failed ignition
12Low flame sense
13Flame lost
14Unexpected flame
20Twinning fault
22Main limit open
23HALC limit open (HALC LIMIT OPEN)
26Line and neutral reversed
30Open fuse
33Rollout switch (MRLC) open
44Low pressure switch closed (stuck)
45Low pressure switch open - inducer high speed
46Low pressure switch open - inducer low speed
55Pressure switch stuck closed
57Pressure switch stuck open
58Water sense circuit open
59Water sensed / blocked drain
60Blower fault - running (BLWR FLT-RUN)
66Blower overspeed (BLOWER OVRSPEED)
68No blower communication (NO BLWR COMM)
82Supply air sensor fault (SA SENSOR FLT)
84Outdoor air sensor fault
AFAirflow readout (pushbutton status menu)
Blank thermostat text areaThermostat text area blank - system found OK
Blinking decimal pointAirflow readout - blinks of right decimal point
CCooling or heat-pump heat (compressor call)
cd / CdDehumidification cooling
CFM LED blinksCFM LED blink count = target airflow
d1No shared data (NO SHARED DATA)
d4No valid model data on memory card
d5Card/hardware conflict (CARD-HRD CNFLCT)
d6Blower HP conflict (BLWR HP CNFLCT)
d7Blower manufacturer conflict (BLWR MFG CNFLCT)
d8Old shared data (OLD SHARED DATA)
dFDefrost in progress (dual fuel)
FContinuous fan on
FAULT HISTORY menuFurnace user menu - FAULT HISTORY
Fault recallPower-up replay of the last three faults
Fault recall - last 5Power-up replay of the last five faults
FIXED FIRE RATEForced low or high fire test (SETUP menu)
FLFault history (pushbutton status menu)
Flame LED offNo flame sensed (troubleshooting aid)
Flame LED slow blinkAmber flame LED - marginal flame sense
Flame LED steady onAmber flame LED steady - normal flame sensed
FrFire rate readout (pushbutton status menu)
FURNACE FOUNDThermostat start-up message - equipment found
HGas heat on
h (lowercase)Low-fire gas heat on
h flashingCalibrating (CALIBRATE-NO V)
HPHeat-pump heat running (dual fuel)
Learn buttonLearn button - RX LED rapid blink test
Power LED onPower LED on - control has 24 VAC
rLockout indicator
RX LED blinkingGreen RX LED - network traffic present
SEARCHINGThermostat start-up message - searching
SETUP menuFurnace user menu - SETUP
STAT LED double blinkRed STAT LED - two slow blinks at power-up
STATUS 1 menuFurnace user menu - STATUS 1
STATUS 2 menuFurnace user menu - STATUS 2
Status LED steady onStatus LED steady - normal (RGRM/RGTM)
Top and bottom bars (right digit)Fault history cleared confirmation
trTemperature rise readout (pushbutton status menu)
UIUnit input readout (pushbutton status menu)
UNIT INFO menuFurnace user menu - UNIT INFO

Rheem Heat Pump error codes

CodeMeaning
0Standby - no call for operation
01Long run time (compressor)
1 flash (L terminal)L-terminal fault output: Long run cycle or low pressure
02High side fault (compressor limit opened 4 times)
2 flashes (L terminal)L-terminal fault output: High pressure control trip
03Short cycling
3 flashes (L terminal)L-terminal fault output: Unit short cycling
4 flashes (L terminal)L-terminal fault output: Locked rotor
05Open circuit - compressor will not run
5 flashes (L terminal)L-terminal fault output: Compressor will not run, open circuit
06Compressor open start circuit
6 flashes (L terminal)L-terminal fault output: Open start circuit
07Compressor open run circuit
7 flashes (L terminal)L-terminal fault output: Open run circuit
8 flashes (L terminal)L-terminal fault output: Control mis-operation
09Low secondary (control) voltage
9 flashes (L terminal)L-terminal fault output: Low control voltage
21Low pressure control (LPC) open
27Low line voltage or no line voltage
28High line voltage
29High pressure control (HPC) open
30ICC fuse open
80Low airflow
83Condenser coil temperature sensor fault
84Outdoor ambient temperature sensor fault
90Communication fault
93Internal control fault
cFirst-stage cooling
C (upper case)Second-stage cooling
dDefrost active
d1No shared data
d3Airflow CFM mismatch
d4Memory card invalid for device
d8Old shared data
Defrost test (SW2)Forced defrost test
Fault recall mode (TEST + SW2)Review stored faults on the ICC display
Flashing c / C / h / HAnti-short-cycle (3 min) or minimum-run (30 s) timer active
hFirst-stage heat pump heating
H (upper case)Second-stage heat pump heating
L4Locked rotor lockout
L6Open start circuit lockout
L7Open run circuit lockout
L21Low pressure control lockout
PCompressor protector trip
tTest mode active
Test mode (TEST button)ICC test mode and short-cycle bypass
Y1 LED solid redRed Y1 LED - call for compressor operation

Find codes by Rheem model

96V

(-)96V060(-)96V070(-)96V085(-)96V10096VA06096VA07096VA08596VA100

Rheem 90RJ/90TJ 90 Plus

90RJ0490RJ0690RJ0790RJ0990RJ1090RJ1290TJ0490TJ0690TJ0790TJ0990TJ1090TJ12

96MDV

96MDV06096MDV07096MDV08596MDV100

R96V/96MDV

96MDV115D50A

R95P

R95PA0401317MSAR95PA0601317MSAR95PA0701317MSAR95PA0851521MSAR95PA1001521MSAR95PA1151524MSA

Rheem/Ruud 802P / 80MDP 80% two-stage furnace (UT 1028-928 IFC)

R802PA050314MSAR802PA075417MSAR802PA100521MSAR802PA125524MSAR802PA150524MSA

RGPE/RGLE

RGLE-05(-)BMKRRGLE-07(-)AMKRRGLE-07(-)BRQRRGLE-10(-)BRMRRGLE-12(-)ARMRRGPE-05(-)BMKRRGPE-07(-)AMKRRGPE-07(-)BRQRRGPE-10(-)BRMRRGPE-12(-)ARMR

Rheem (-)GRC/(-)GTC 90 Plus

RGRC-04EMAESRGRC-06EMAESRGRC-07EMAESRGRC-07ERBGSRGRC-09EZAJSRGRC-10EZAJSRGTC-04EMAESRGTC-06EMAESRGTC-07ERBGSRGTC-09EZAJSRGTC-10ERBJS

Rheem RGRM/RGTM 90 Plus

RGRM-04RGRM-06RGRM-07RGRM-09RGRM-10RGRM-12RGTM-06RGTM-07RGTM-09RGTM-10

Rheem/Ruud PRL-JEC heat pump (Comfort Control2 ICC)

RPRL-024JECRPRL-036JECRPRL-048JECRPRL-060JEC

Rheem troubleshooting guides

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.