Rheem Error Code 11: Failed ignition (Furnace)

Updated · by Aurora Star Tech Inc.

Rheem error code 11 on a furnace means: Failed ignition. It is also called Rheem diagnostic code 11.

High severityFurnaceRheem/Ruud 802P / 80MDP 80% two-stage furnace (UT 1028-928 IFC) · R95P · RGPE/RGLE · R96V/96MDV

Homeowner? What Rheem code 11 means for you

Call a technician Your furnace is reporting: Failed ignition. The furnace has locked out or cannot run properly. One reset is fine; if the code comes back, it needs a licensed technician to find the cause.

Safe things you can check yourself

  • Check the thermostat: right mode (Heat or Cool), set a few degrees past room temperature, and fresh batteries if it uses them.
  • Make sure the unit has power: its on/off switch (often looks like a light switch near the unit) is ON and the breaker in the electrical panel is not tripped.
  • Make sure the furnace front door or panel is closed properly; many furnaces will not run with the door switch open.
  • Look at the air filter. If it is grey and clogged, replace it; a blocked filter causes many shutdowns.
  • Outside, make sure the intake and exhaust pipes or vent cap are not blocked by snow, ice, leaves or a nest.
  • Check that the gas valve next to the furnace is open (handle in line with the pipe). Do not force it.
  • Try one reset: turn the power off for 30 seconds, then back on. If the code comes back, stop resetting and call a technician.

Call (647) 657-2977Book a service call

Licensed technicians serving Vaughan, Toronto and the GTA.

What does Rheem error code 11 mean?

No flame proven during the ignition trial. The system tries 4 times, then goes into a 1-hour lockout (10 and 11 alternate on 802P/R95P). 802P: valve opens on low fire for 8 seconds, spark up to 7 seconds, flame must prove for 1 second. R95P/RGPE: valve powered about 7 seconds per trial. RGPE/RGLE: not stored back-to-back in the fault buffer.

Applies to: 802P/80MDP (802PA050-150); R95P (R95PA040-115); RGPE/RGLE 2-stage 80+

Common causes of Rheem code 11

  • No gas, manual valve switch off, or low gas pressure
  • Spark igniter not sparking, cracked, disconnected or misplaced
  • Dirty flame sensor or poor sensor wiring

A technician checks these and 4 other possible causes on site before replacing any part.

Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

Rheem models that use code 11

Show all 22 models

96MDV115D50AR95PA0401317MSAR95PA0601317MSAR95PA0701317MSAR95PA0851521MSAR95PA1001521MSAR95PA1151524MSAR802PA050314MSAR802PA075417MSAR802PA100521MSAR802PA125524MSAR802PA150524MSARGLE-05(-)BMKRRGLE-07(-)AMKRRGLE-07(-)BRQRRGLE-10(-)BRMRRGLE-12(-)ARMRRGPE-05(-)BMKRRGPE-07(-)AMKRRGPE-07(-)BRQRRGPE-10(-)BRMRRGPE-12(-)ARMR

Other Rheem Furnace codes

CodeMeaning
2 WK HIST / LIFE HIST menusFurnace user menus - run-time histories
3 blinksLimit circuit open
4 blinksPressure switch circuit closed (stuck closed)
5 blinksTwinning fault (optional)
6 blinksLine and neutral reversed
10One-hour lockout
12Low flame sense
13Flame lost
14Unexpected flame
20Twinning fault
22Main limit open
23HALC limit open (HALC LIMIT OPEN)

All Rheem Furnace error codes →

Rheem code 11: homeowner questions

What does Rheem code 11 mean?

Failed ignition. No flame proven during the ignition trial. The system tries 4 times, then goes into a 1-hour lockout (10 and 11 alternate on 802P/R95P). 802P: valve opens on low fire for 8 seconds, spark up to 7 seconds, flame must prove for 1 second.…

Is it safe to keep using my furnace with code 11?

It depends on the cause. The furnace has locked out or cannot run properly. One reset is fine; if the code comes back, it needs a licensed technician to find the cause.

Can I reset Rheem code 11 myself?

You can try one reset (power off for 30 seconds, then on). If Rheem code 11 comes back, the cause is still there and a licensed technician should check it.

Who can fix Rheem code 11 near me?

Aurora Star Tech Inc. repairs Rheem furnaces in Vaughan, Toronto and across the GTA. Call (647) 657-2977 or book a service call online.

Homeowner help: Furnace Not Turning On: What to Check · Furnace Blinking Light: What the Flash Codes Mean

Troubleshooting guides

Source: 802P: 92-24161-146-02, Diagnostics and Fault Codes table, p.40, 51; R95P: Diagnostics and Fault Codes table, p.87 (PDF p.91); RGPE/RGLE: Table 16 p.49 / Table 20; Fig. 45 p.63. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.

Emergency Furnace Repair

647-657-2977