Rheem Furnace: Checking furnace input rate
Checking furnace input rate on a Rheem furnace: Clocking the gas meter to confirm the Rheem 96V/96MDV isn't over-fired. Input must never go above the rating plate.
Applies to: 96V and 96MDV gas furnaces
Common causes of checking furnace input rate
- Manifold pressure set too high
- Oversized orifices installed
- Unadjusted for altitude or a different heating value than expected
How to fix checking furnace input rate: step by step
- Make sure all other gas appliances are off, except pilot burners, so the meter reads only the furnace.
- Start the furnace and time the meter for one cubic foot of gas.
- Compare the calculated input with the rating plate and the input rate table, because the numbers should agree.
- If input is high, adjust manifold pressure or orifice size.
- Never set input above the rating plate.
- This is gas work for a licensed technician. Recheck input after any adjustment.
If the unit shows an error code, look it up: Rheem Furnace codes
Models
96V
(-)96V060(-)96V070(-)96V085(-)96V10096VA06096VA07096VA08596VA100
96MDV
96MDV06096MDV07096MDV08596MDV100
Source: 96V installation instructions, p. 103. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.