Rheem Error Code 22: Main limit open (Furnace)
Rheem error code 22 on a furnace means: Main limit open. It is also called Rheem diagnostic code 22.
Homeowner? What Rheem code 22 means for you
Call a technician Your furnace is reporting: Main limit open. The furnace has locked out or cannot run properly. One reset is fine; if the code comes back, it needs a licensed technician to find the cause.
Safe things you can check yourself
- Check the thermostat: right mode (Heat or Cool), set a few degrees past room temperature, and fresh batteries if it uses them.
- Make sure the unit has power: its on/off switch (often looks like a light switch near the unit) is ON and the breaker in the electrical panel is not tripped.
- Make sure the furnace front door or panel is closed properly; many furnaces will not run with the door switch open.
- Look at the air filter. If it is grey and clogged, replace it; a blocked filter causes many shutdowns.
- Outside, make sure the intake and exhaust pipes or vent cap are not blocked by snow, ice, leaves or a nest.
- Check that the gas valve next to the furnace is open (handle in line with the pipe). Do not force it.
- Try one reset: turn the power off for 30 seconds, then back on. If the code comes back, stop resetting and call a technician.
Call (647) 657-2977Book a service call
Licensed technicians serving Vaughan, Toronto and the GTA.
What does Rheem error code 22 mean?
Main high-limit circuit is open (supply air too hot / poor airflow). 802P/R95P: if open more than 150 seconds during a heat call, 61 and 22 alternate (dead blower) until it recloses. RGPE/RGLE: an open main limit can indicate excessive duct static; thermostat shows Call For Service / CHECK FURNACE.
Applies to: 802P/80MDP (802PA050-150); R95P (R95PA040-115); RGPE/RGLE 2-stage 80+
Common causes of Rheem code 22
- Dirty or restricted filter or cooling coil
- Closed registers/dampers, undersized or restricted ducts, high static
- Blower problem: wrong speed tap, bad capacitor, dirty wheel, failing motor, low voltage
A technician checks these and 2 other possible causes on site before replacing any part.
Rheem models that use code 22
Show all 22 models
96MDV115D50AR95PA0401317MSAR95PA0601317MSAR95PA0701317MSAR95PA0851521MSAR95PA1001521MSAR95PA1151524MSAR802PA050314MSAR802PA075417MSAR802PA100521MSAR802PA125524MSAR802PA150524MSARGLE-05(-)BMKRRGLE-07(-)AMKRRGLE-07(-)BRQRRGLE-10(-)BRMRRGLE-12(-)ARMRRGPE-05(-)BMKRRGPE-07(-)AMKRRGPE-07(-)BRQRRGPE-10(-)BRMRRGPE-12(-)ARMR
Other Rheem Furnace codes
All Rheem Furnace error codes →
Rheem code 22: homeowner questions
What does Rheem code 22 mean?
Main limit open. Main high-limit circuit is open (supply air too hot / poor airflow). 802P/R95P: if open more than 150 seconds during a heat call, 61 and 22 alternate (dead blower) until it recloses. RGPE/RGLE: an open main limit can indicate excessive…
Is it safe to keep using my furnace with code 22?
It depends on the cause. The furnace has locked out or cannot run properly. One reset is fine; if the code comes back, it needs a licensed technician to find the cause.
Can I reset Rheem code 22 myself?
You can try one reset (power off for 30 seconds, then on). If Rheem code 22 comes back, the cause is still there and a licensed technician should check it.
Who can fix Rheem code 22 near me?
Aurora Star Tech Inc. repairs Rheem furnaces in Vaughan, Toronto and across the GTA. Call (647) 657-2977 or book a service call online.
Homeowner help: Furnace Not Turning On: What to Check · Furnace Blinking Light: What the Flash Codes Mean
Troubleshooting guides
- Blower cycles on and off All brands · Furnace
- Blower runs, not enough heat All brands · Furnace
- Blowing cold air All brands · Furnace
- Board shows "flame sensed with no call for heat" All brands · Furnace
- Can't pull oil (distance/lift) All brands · Furnace
- CO in flue / poor combustion numbers All brands · Furnace
- Cold air blast at start / blower never stops All brands · Furnace
- Combustion gas / odour in house, flu-like symptoms All brands · Furnace
Source: 802P: 92-24161-146-02, Diagnostics and Fault Codes table, p.40, 48, 51; R95P: Diagnostics and Fault Codes table, p.87 (PDF p.91); RGPE/RGLE: Table 16 p.49 / Table 20; Fig. 45 p.63; user menus p.52. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.