Rheem Furnace: Check airflow with a temperature rise measurement

Updated · by Aurora Star Tech Inc.

Check airflow with a temperature rise measurement on a Rheem furnace: Use this check to confirm airflow over the heat exchanger. Temperature rise should sit near the middle of the range on the furnace nameplate. Too high means airflow is too low. Too low means airflow is too high.

Homeowner with a furnace problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Airflow setup on R96V furnace

Common causes of check airflow with a temperature rise measurement

  • Restricted duct system or undersized ducts (high rise)
  • Blower speed tap set too low (high rise)
  • Blower speed tap set too high (low rise)

How to fix check airflow with a temperature rise measurement: step by step

  1. Place a thermometer in the supply duct as close to the furnace as possible, out of direct line from the heat exchanger.
  2. Place a thermometer in the return duct as close to the furnace as possible.
  3. Run the furnace at least 15 minutes in gas heat mode.
  4. When the supply temperature stops rising (about five minutes), subtract return air temperature from supply air temperature. The result is the temperature rise.
  5. Compare the result to the approved range on the nameplate. Adjust the rise to the middle of the range as closely as possible. Never let it go above or below the range.
  6. If the rise is above the range, raise airflow by increasing blower speed, removing duct restrictions, or adding supply or return duct.
  7. If the rise is below the range, use a lower speed tap on the multi-speed blower.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Rheem Furnace codes

Models

96V

(-)96V060(-)96V070(-)96V085(-)96V10096VA06096VA07096VA08596VA100

96MDV

96MDV06096MDV07096MDV08596MDV100

Source: Rheem 96V installation manual, p. 105. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.