Check vent length with elbows on a Rheem furnace: Every vent system has a maximum equivalent length, and fittings count as extra length. This is a worked example for the 60 KBTU/H direct vent model using 2 in pipe. Do the math before you cut pipe, not after, and keep the fitting type in mind, because swapping long sweep elbows for standard ones can push a run over the limit. Vent length is a code and safety item. If the total is over the maximum, change the layout or pipe size rather than hoping it works.

Homeowner with a furnace problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: 60 KBTU/H direct vent furnace, 2 in pipe

Common causes of check vent length with elbows

  • New direct vent install with many elbows
  • Replacement furnace on an existing vent run
  • Change from long sweep to standard elbows
  • Vent that pressure switch trips on because it is too long

How to fix check vent length with elbows: step by step

  1. Add up straight pipe length (example: 31 ft)
  2. Multiply the number of long sweep 90 degree elbows by 5 ft (example: 5 elbows = 25 ft)
  3. Add straight pipe and elbow equivalents (example: 56 ft)
  4. Compare to the model maximum (65 ft for 60 KBTU/H). Acceptable if at or below
  5. If standard elbows are used instead (10 ft each), the same run becomes 81 ft and is not acceptable
  6. If over the limit, re-route, remove elbows or step up the pipe size per the manual
  7. Recheck the total after any change to the layout
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Rheem Furnace codes

Models

96V

(-)96V060(-)96V070(-)96V085(-)96V10096VA06096VA07096VA08596VA100

96MDV

96MDV06096MDV07096MDV08596MDV100

Source: 96V Series installation instructions, p. 48. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.