Goodman Error Codes & Diagnostic Codes

Updated · by Aurora Star Tech Inc.

Goodman error codes and diagnostic codes: look up a code to see what it means, the likely causes and the steps to fix it.

Goodman error codes by equipment type

Goodman Air Conditioner error codes

CodeMeaning
01Low side fault or low pressure switch trip
02High side fault or high pressure switch trip
03Short cycling
04Locked rotor
05Open circuit - compressor off over 4 hours
06Open start circuit
07Open run circuit
08No line voltage
09Low 24 V control voltage
b0Indoor blower not running when it should be
b9Indoor airflow lower than requested
Comfort Alert 1Yellow ALERT 1 flash - long run time
Comfort Alert 2Yellow ALERT 2 flashes - system pressure trip
Comfort Alert 3Yellow ALERT 3 flashes - short cycling
Comfort Alert 4Yellow ALERT 4 flashes - locked rotor
Comfort Alert 5Yellow ALERT 5 flashes - open circuit
Comfort Alert 6Yellow ALERT 6 flashes - open start circuit
Comfort Alert 7Yellow ALERT 7 flashes - open run circuit
Comfort Alert 9Yellow ALERT 9 flashes - low control voltage
Comfort Alert last alert recallLast alert code replayed after power-up
Comfort Alert POWERGreen POWER - module has power
Comfort Alert TRIPRed TRIP LED - call present but compressor not running
Comfort Alert TRIP+ALERTTRIP and ALERT LEDs flashing together - control voltage too low
CoreSense 1Yellow 1 flash - long run time (low side)
CoreSense 2Pressure trip - yellow 2 flashes (red 2 = lockout)
CoreSense 3Short cycling / pressure switch cycling - yellow 3 (red 3 = lockout)
CoreSense 4Locked rotor - yellow 4 (red 4 = lockout)
CoreSense 5Moderate run trip - yellow 5 (red 5 = lockout)
CoreSense 9Red 9 flashes - PROT output overcurrent
CoreSense solid redSolid red TRIP - call present but compressor not running
CoreSense solid yellowSolid yellow RUN - module powered, operating normally
d0No shared data on the network
d1Invalid shared data on the network
d2System mismatch - indoor unit cannot supply required airflow
d3Configuration mismatch - shared data does not match hardware
d4Shared data from the loader rejected
E5Outdoor control low-voltage fuse open
EEOutdoor control fault - compressor relay contacts welded
L1Lockout - low pressure switch tripped 3 times
L2Lockout - high pressure switch tripped 3 times
L7Lockout - open run circuit detected 4 times
L8Low line voltage
P0Compressor protector open
Yellow 1 flashLow side fault / low pressure trip / low pressure lockout (older ComfortNet board)
Yellow 2 flashesHigh side fault / high pressure trip / high pressure lockout (older ComfortNet board)
Yellow 3 flashesShort cycling (older ComfortNet board)
Yellow 4 flashesLocked rotor (older ComfortNet board)
Yellow 5 flashesOpen circuit (older ComfortNet board)
Yellow 6 flashesOpen start circuit / lockout (older ComfortNet board)
Yellow 7 flashesOpen run circuit / lockout (older ComfortNet board)
Yellow 8 flashesLow or high line voltage (older ComfortNet board)
Yellow 9 flashesLow 24 V control voltage (older ComfortNet board)
Yellow ON + Red ONCompressor protector open (older ComfortNet board)

Goodman Air Handler error codes

CodeMeaning
1ACCompressor cooling, low stage (non-comm)
2aCCompressor cooling, high stage (non-comm)
5rShared data revision
ACCompressor cooling, single stage (non-comm)
AC1Compressor cooling, low stage (comm)
AC2Compressor cooling, high stage (comm)
AxxAirflow readout (A08 = 800 CFM)
CrControl firmware revision
df1Defrost, low-stage electric heat
df2Defrost, high-stage electric heat
dftDefrost, single-stage electric heat (non-comm)
dHUDehumidification
E05Air handler fuse open
Eb0Blower motor not running with a demand present
Eb1Control lost communication with the blower motor
Eb2Motor horsepower does not match shared data
Eb4Blower motor lost rotor control or high current
Eb5Blower motor failed to start 10 times
Eb6Blower shut down for voltage or power module temperature
Eb7Blower motor missing shared data / failed to start 40 times
Eb9Airflow lower than demanded
EC1Communication error with the outdoor unit
Ed1Invalid shared data
Ed4Shared data rejected by the control
FAnConstant fan
FCLFault recall (outdoor communicating units)
Flashing optionMenu option flashing = not yet selected
HPCompressor heat, single stage
HP1Compressor heat, low stage (comm)
HP2Compressor heat, high stage (comm)
HtElectric heat, single stage
Ht1Electric heat (Ht1)
Ht2Electric heat, high stage
IdlIdle - no call
L6FFault recall (furnace-type menu)
LrnRestart indoor-outdoor communication
RDS 4 flashesR32 sensor internal fault
RDS fast flashR-32 leak alarm (or system verification test)
RDS slow flashNormal operation - leak detection OK
RDS steady onDelay mode after leak alarm or fault
RDS test modeSystem verification test (simulated leak)
Rx LED rapid flashGreen receive LED rapid flashing - normal network traffic

Goodman Furnace error codes

CodeMeaning
1 flashLockout - three failed ignition tries
1ACCooling, low stage
2 flashesPressure switch stuck closed
2ACCooling, high stage
3 flashesPressure switch stuck open
4 flashesPrimary or auxiliary limit open
5 flashesFlame sensed with no call for heat
6 flashesRollout limit open or control fuse blown
7 flashesLow flame signal
8 flashesIgniter relay fault
9 flashesTwinning fault
10 flashesOpen fuse - no 24 V at the control
11 flashesIgniter open
12 flashesInducer relay fault
88Power-up self check
ACCooling, single stage
AC1Cooling, low stage (communicating)
AC2Cooling, high stage (communicating)
AxxAirflow readout
b0Blower motor not running
b1Lost communication with blower motor
b2Blower motor size does not match model data
b3Blower motor limiting (power, temperature or speed)
b4Blower motor trip (lost rotor control or high current)
b5Blower motor locked rotor
b6Blower motor over/under voltage or over temperature
b7Blower motor missing parameters
b9Low indoor airflow
C1Low-stage cooling
C2High-stage cooling
CFM readoutAirflow number (CFM / 100)
CFSComfort setting
CrCode release number
d0No shared data on the control
d4Memory card data rejected
dF1Defrost, low-stage gas heat
dF2Defrost, high-stage gas heat
dHLDehumidify logic input level
dHUDehumidifier on
E0Lockout - ignition failed 3 times
E1Low-stage pressure switch closed at start of heat
E2Low-stage pressure switch will not close
E3High limit or rollout limit open
E4Flame sensed with no call for heat
E5Control fuse open
E6Low flame signal
E7Igniter circuit fault
E8High-stage pressure switch closed at start of heat
E9High-stage pressure switch will not close
E10Grounding fault / poor neutral connection
E11Flame rollout switch open
E12Redundant relay open
E13Redundant relay stuck closed
EA115 V polarity reversed
Eb0Blower motor not running
Eb1Lost communication with blower motor
Eb2Blower motor hp does not match model data
Eb3Blower motor running in power, temperature or speed limit
Eb4Blower motor current trip or lost rotor control
Eb5Blower motor locked rotor
Eb7Blower motor missing parameters
Eb9Inadequate airflow
Ec1Network communication alarm
Ec2E-module network communication alarm
Ec3Bluetooth module network communication alarm
Ed0No shared data on the network
Ed1Invalid data on network
Ed4Memory card data rejected
Ed5Invalid downloaded firmware
Ed6Unrecognized data ID
EE0Lockout - too many ignition retries (3)
EE1Pressure switch closed at start of heating cycle
EE2Pressure switch did not close (inducer runs, no ignition)
EE3High (primary) limit open
EE4Flame sensed with no call for heat
EE5Open fuse (short in low voltage wiring)
EE6Low flame signal
EE8High-stage pressure switch closed at start of heating cycle
EE9High-stage pressure switch did not close
EEAReversed line polarity or grounding error
EEbExternal gas valve error - valve not energized when it should be
EECInternal gas valve error - valve energized when it should not be
EEdCondensate or auxiliary alarm switch open
EEEInternal control fault (IRQ loss)
EEFCondensate switch open
EEHTwinning error
EEJInducer relay error
EELIgniter relay / igniter circuit fault
EEnIgniter open
EOLOEM test mode
ErrActive alarm menu
FContinuous fan
FAnContinuous fan
gAFGas heat airflow
gbPBackup heat balance points
gFdGas heat fan off delay
gHGas heat, single stage
gH1Gas heat, low stage
gH2Gas heat, high stage
gndGas heat fan on delay
gPtGas pressure test
gStGas heat stage multiplier
gtFGas heat trim factor
HEdHumidifier enable
HIHigh-stage heat
HPHeat pump heat, single stage
HP1Heat pump heat, low stage
HP2Heat pump heat, high stage
HUdHumidifier on
IdLIdle - no call
L0Low-stage heat
L6FLast 6 faults (view and clear)
LED offNo LED - no power or control failure
LED steady onNormal operation
LrnLearn menu
OPNormal - waiting for a call
Rapid flashReversed polarity
Red LED 1 flashRed communications LED 1 flash - communication failure
Red LED 2 flashesRed communications LED 2 flashes - reset in progress
Red LED offRed communications LED off - normal
rFdReset to factory defaults
Rx LED 1 steady flashGreen receive LED single steady flash - no network found
Rx LED offGreen receive LED off - no power or communications error
Rx LED on solidGreen receive LED on solid - data lines miswired or shorted
Rx LED rapid flashGreen receive LED rapid flashing - normal network traffic
SH1Special heat relay 1
SH2Special heat relay 2
SrShared data revision
uACInverter cooling
uHPInverter heat pump heat
utLVentilator on

Goodman Heat Pump error codes

CodeMeaning
01Low side fault or low pressure switch trip
02High side fault or high pressure switch trip
03Short cycling
04Locked rotor
05Open circuit - compressor off over 4 hours
07Open run circuit
09Low 24 V control voltage
A2Outdoor air temperature sensor fault
A3Outdoor coil temperature sensor fault
b0Indoor blower not running when it should be
b9Indoor airflow lower than requested
CoreSense 1Yellow 1 flash - long run time (low side)
CoreSense 2Pressure trip - yellow 2 flashes (red 2 = lockout)
CoreSense 3Short cycling / pressure switch cycling - yellow 3 (red 3 = lockout)
CoreSense 4Locked rotor - yellow 4 (red 4 = lockout)
CoreSense 5Moderate run trip - yellow 5 (red 5 = lockout)
CoreSense 9Red 9 flashes - PROT output overcurrent
CoreSense solid redSolid red TRIP - call present but compressor not running
CoreSense solid yellowSolid yellow RUN - module powered, operating normally
d0No shared data on the network
d1Invalid shared data on the network
d2System mismatch - indoor unit cannot supply required airflow
d3Configuration mismatch - shared data does not match hardware
d4Shared data from the loader rejected
E5Outdoor control low-voltage fuse open
EEOutdoor control fault - compressor relay contacts welded
H8High line voltage
L1Lockout - low pressure switch tripped 3 times
L2Lockout - high pressure switch tripped 3 times
L6Lockout - open start circuit detected 4 times
L7Lockout - open run circuit detected 4 times
L8Low line voltage
P0Compressor protector open
Yellow 1 flashLow side fault / low pressure trip / low pressure lockout (older ComfortNet board)
Yellow 2 flashesHigh side fault / high pressure trip / high pressure lockout (older ComfortNet board)
Yellow 3 flashesShort cycling (older ComfortNet board)
Yellow 4 flashesLocked rotor (older ComfortNet board)
Yellow 5 flashesOpen circuit (older ComfortNet board)
Yellow 6 flashesOpen start circuit / lockout (older ComfortNet board)
Yellow 7 flashesOpen run circuit / lockout (older ComfortNet board)
Yellow 8 flashesLow or high line voltage (older ComfortNet board)
Yellow ON + Red ONCompressor protector open (older ComfortNet board)

Find codes by Goodman model

Goodman/Amana *MVC96 (34.5 in. chassis)

*CVC960403BNB**CVC960603BNB**CVC960804CNB**CVC961005CNB**CVC961205DNB**MVC960403BNB**MVC960603BNB**MVC960803BNB**MVC960804CNB**MVC961005CNB**MVC961005DNB**MVC961205DNB*ACVC96AMVC96GCVC96GMVC96

Goodman/Amana GM9C96/AM9C96

AC9C96AM9C96AM9C960303ANGC9C96GM9C96GM9C960303AN

Goodman/Amana GM9S80/AM9S80

AC9S800403ANAC9S800603ANAC9S800804BNAC9S800805CNAC9S801005CNAM9S800403ANAM9S800603ANAM9S800603BNAM9S800604BNAM9S800803BNAM9S800804BNAM9S800804CNAM9S800805CNAM9S801005CNAM9S801205DNGC9S800403ANGC9S800603ANGC9S800804BNGC9S800805CNGC9S801005CNGM9S800403ANGM9S800603ANGM9S800603BNGM9S800604BNGM9S800803BNGM9S800804BNGM9S800804CNGM9S800805CNGM9S801005CNGM9S801205DN

Goodman/Amana GM9S96/AM9S96

AC9S960403BNAC9S960603BNAC9S960804CNAC9S961005CNAC9S961205CNAC9S961205DNAM9S920403ANAM9S920603BNAM9S920803BNAM9S920804CNAM9S920805CNAM9S921004CNAM9S921005CNAM9S921205DNAM9S960403ANAM9S960603BNAM9S960803BNAM9S960804CNAM9S960805CNAM9S961004CNAM9S961005CNAM9S961205DNGC9S960403BNGC9S960603BNGC9S960804CNGC9S961005CNGC9S961205CNGC9S961205DNGM9S920403ANGM9S920603BNGM9S920803BNGM9S920804CNGM9S920805CNGM9S921004CNGM9S921005CNGM9S921205DNGM9S960403ANGM9S960603BNGM9S960803BNGM9S960804CNGM9S960805CNGM9S961004CNGM9S961005CNGM9S961205DN

Goodman/Amana *MES9 single-stage

ACES96ACES960403BNAAACES960603BNAAACES960804CNAAACES961005CNAAACES961205DNAAAMES92AMES96AMES920403ANAAAMES920603BNAAAMES920803BNAAAMES920804CNAAAMES920805CNAAAMES921004CNAAAMES921005CNAAAMES921205DNAAAMES960403ANAAAMES960603BNAAAMES960803BNAAAMES960804CNAAAMES960805CNAAAMES961005CNAAAMES961205DNAAGCES96GCES960403BNAAGCES960603BNAAGCES960804CNAAGCES961005CNAAGCES961205DNAAGMES92GMES96GMES920403ANAAGMES920603BNAAGMES920803BNAAGMES920804CNAAGMES920805CNAAGMES921004CNAAGMES921005CNAAGMES921205DNAAGMES960403ANAAGMES960603BNAAGMES960803BNAAGMES960804CNAAGMES960805CNAAGMES961005CNAAGMES961205DNAAVCES96VCES960403BNAAVCES960603BNAAVCES960804CNAAVCES961005CNAAVMES96VMES960403ANAAVMES960603BNAAVMES960803BNAAVMES960804CNAAVMES961005CNAA

Goodman/Amana R-32 AMST/AWSF/ACSF air handlers

ACSF****13**AAAMST***U1300AAAWSF****13**AAAWST****13**AA

Goodman/Amana R-32 GLXS/ALXS

ALXS3BN**10AAALXS4BA**10AAALXS4NA**10AAALXS5BA**10AAGLXS3BN**10AAGLXS4BA**10AAGLXS4MA**10AAGLXS5BA**10AA

Goodman/Amana R-32 GLZS/ALZS

ALZS4BA**10AAALZS4NA**10AAALZS5BA**10AAGLZS4BA**10AAGLZS4MA**10AAGLZS5BA**10AA

Goodman/Amana R-410A GSX/ASX/DSX (ANX/SSX/VSX)

ANX130181ANX130241ANX130301ANX130361ANX130421ANX130481ANX130601ANX130611ANX140181ANX140191ANX140241ANX140251ANX140301ANX140361ANX140371ANX140421ANX140431ANX140481ANX140601ASX180**1ABASX130181ASX130241ASX130301ASX130361ASX130421ASX130481ASX130601ASX130611ASX140181ASX140191ASX140241ASX140251ASX140301ASX140311ASX140361ASX140371ASX140421ASX140431ASX140481ASX140601ASX160181ASX160241ASX160301ASX160311ASX160361ASX160371ASX160421ASX160481ASX160601ASX160611ASXH5***10DSX160241DSX160361GSX16A181GSX16A241GSX16A301GSX16A361GSX16A421GSX16A481GSX16A601GSX16S181GSX16S241GSX16S301GSX16S361GSX16S421GSX16S481GSX110903GSX110904GSX111203GSX111204GSX130181GSX130241GSX130301GSX130361GSX130363GSX130371GSX130421GSX130481GSX130483GSX130484GSX130601GSX130603GSX130604GSX130611GSX140181GSX140191GSX140241GSX140251GSX140301GSX140311GSX140361GSX140371GSX140421GSX140431GSX140481GSX140601GSX160181GSX160241GSX160301GSX160311GSX160361GSX160371GSX160421GSX160481GSX160601GSX160611GSXH5***10SSX140181SSX140241SSX140301SSX140361SSX140421SSX140481SSX140601SSX160241SSX160301SSX160361SSX160421SSX160481SSX160591SSX160601VSX130181VSX130241VSX130301VSX130361VSX130371VSX130421VSX130481VSX130601VSX130611VSX140181VSX140191VSX140241VSX140251VSX140301VSX140311VSX140361VSX140371VSX140421VSX140431VSX140481VSX140601

Goodman/Amana R-410A GSZ/ASZ/DSZ (ANZ/SSZ/VSZ)

ANZ130181ANZ130241ANZ130301ANZ130361ANZ130421ANZ130481ANZ130601ANZ140181ANZ140241ANZ140301ANZ140361ANZ140421ANZ140481ANZ140491ANZ140601ASZ130181ASZ130241ASZ130301ASZ130361ASZ130421ASZ130481ASZ130601ASZ140181ASZ140241ASZ140301ASZ140361ASZ140381ASZ140421ASZ140481ASZ140491ASZ140601ASZ160181ASZ160241ASZ160301ASZ160361ASZ160421ASZ160481ASZ160601ASZ180361ASZ180481ASZ180601ASZH5***10DSZ160241DSZ160361DSZ160481DSZ160601DSZ180361DSZ180481DSZ180601GSZ110903GSZ110904GSZ111203GSZ111204GSZ130181GSZ130191GSZ130241GSZ130251GSZ130301GSZ130311GSZ130361GSZ130363GSZ130371GSZ130421GSZ130481GSZ130483GSZ130484GSZ130601GSZ140181GSZ140241GSZ140301GSZ140361GSZ140371GSZ140421GSZ140481GSZ140491GSZ140601GSZ160181GSZ160241GSZ160301GSZ160361GSZ160421GSZ160481GSZ160601GSZH5***10SSZ140181SSZ140191SSZ140241SSZ140251SSZ140301SSZ140311SSZ140361SSZ140371SSZ140381SSZ140421SSZ140481SSZ140601SSZ160241SSZ160361SSZ160421SSZ160481SSZ160601VSZ130181VSZ130241VSZ130301VSZ130361VSZ130421VSZ130481VSZ130601VSZ140181VSZ140241VSZ140301VSZ140361VSZ140421VSZ140481VSZ140491VSZ140601

Goodman/Amana ComfortNet ASXC/GSXC/DSXC

ASXC160241ASXC160361ASXC160481ASXC160601ASXC180241ASXC180361ASXC180481ASXC180601DSXC160241DSXC160361DSXC160481DSXC160601DSXC180361DSXC180481DSXC180601GSXC160241GSXC160361GSXC160481GSXC160601GSXC180241GSXC180361GSXC180481GSXC180601

Goodman/Amana ComfortNet ASZC/GSZC/DSZC

ASZC160241ASZC160361ASZC160421ASZC160481ASZC160601ASZC180241ASZC180361ASZC180481ASZC180601DSZC160241DSZC160361DSZC160481DSZC160601DSZC180361DSZC180481DSZC180601GSZC160241GSZC160361GSZC160481GSZC160601GSZC180241GSZC180361GSZC180481GSZC180601

Goodman/Amana ComfortBridge AVPTC/MBVC

AVPTC25B14AVPTC29B14AVPTC31C14AVPTC31C14ADAVPTC33C14AVPTC35B14AVPTC37B14AVPTC37C14AVPTC37D14AVPTC39C14AVPTC49C14AVPTC49D14AVPTC59C14AVPTC59D14AVPTC61D14AVPTC183014AVPTC313714AVPTC426014MBVC1201MBVC1601MBVC2001

Goodman/Amana *MVC95/*CVC9 two-stage ComfortNet

GCVC90704CXGCVC90905DXGCVC91155DXGCVC950714CXGCVC950915DXGMVC950453BXGMVC950704CXGMVC950905CXGMVC950905DXGMVC951155DX

Goodman troubleshooting guides

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.