Goodman Error Codes & Diagnostic Codes

Updated · by Aurora Star Tech Inc.

Goodman error codes and diagnostic codes: look up a code to see what it means, the likely causes and the steps to fix it.

Goodman error codes by equipment type

Goodman Air Conditioner error codes

CodeMeaning
01Low side fault or low pressure switch trip
02High side fault or high pressure switch trip
03Short cycling
04Locked rotor
05Open circuit - compressor off over 4 hours
06Open start circuit
07Open run circuit
08No line voltage
09Low 24 V control voltage
b0Indoor blower not running when it should be
b9Indoor airflow lower than requested
Comfort Alert 1Yellow ALERT 1 flash - long run time
Comfort Alert 2Yellow ALERT 2 flashes - system pressure trip
Comfort Alert 3Yellow ALERT 3 flashes - short cycling
Comfort Alert 4Yellow ALERT 4 flashes - locked rotor
Comfort Alert 5Yellow ALERT 5 flashes - open circuit
Comfort Alert 6Yellow ALERT 6 flashes - open start circuit
Comfort Alert 7Yellow ALERT 7 flashes - open run circuit
Comfort Alert 9Yellow ALERT 9 flashes - low control voltage
Comfort Alert TRIPRed TRIP LED - call present but compressor not running
Comfort Alert TRIP+ALERTTRIP and ALERT LEDs flashing together - control voltage too low
CoreSense 1Yellow 1 flash - long run time (low side)
CoreSense 2Pressure trip - yellow 2 flashes (red 2 = lockout)
CoreSense 3Short cycling / pressure switch cycling - yellow 3 (red 3 = lockout)
CoreSense 4Locked rotor - yellow 4 (red 4 = lockout)
CoreSense 5Moderate run trip - yellow 5 (red 5 = lockout)
CoreSense 9Red 9 flashes - PROT output overcurrent
CoreSense solid redSolid red TRIP - call present but compressor not running
d0No shared data on the network
d1Invalid shared data on the network
d2System mismatch - indoor unit cannot supply required airflow
d3Configuration mismatch - shared data does not match hardware
d4Shared data from the loader rejected
E5Outdoor control low-voltage fuse open
EEOutdoor control fault - compressor relay contacts welded
H8High line voltage
L1Lockout - low pressure switch tripped 3 times
L2Lockout - high pressure switch tripped 3 times
L6Lockout - open start circuit detected 4 times
L7Lockout - open run circuit detected 4 times
L8Low line voltage
P0Compressor protector open
Yellow 1 flashLow side fault / low pressure trip / low pressure lockout (older ComfortNet board)
Yellow 2 flashesHigh side fault / high pressure trip / high pressure lockout (older ComfortNet board)
Yellow 3 flashesShort cycling (older ComfortNet board)
Yellow 4 flashesLocked rotor (older ComfortNet board)
Yellow 5 flashesOpen circuit (older ComfortNet board)
Yellow 6 flashesOpen start circuit / lockout (older ComfortNet board)
Yellow 7 flashesOpen run circuit / lockout (older ComfortNet board)
Yellow 8 flashesLow or high line voltage (older ComfortNet board)
Yellow 9 flashesLow 24 V control voltage (older ComfortNet board)
Yellow ON + Red ONCompressor protector open (older ComfortNet board)

Goodman Air Handler error codes

CodeMeaning
E0FCondensate switch open - high water in drain pan
E05Air handler fuse open
Eb0Blower motor not running with a demand present
Eb1Control lost communication with the blower motor
Eb2Motor horsepower does not match shared data
Eb3Blower limiting on power, temperature or speed
Eb4Blower motor lost rotor control or high current
Eb5Blower motor failed to start 10 times
Eb6Blower shut down for voltage or power module temperature
Eb7Blower motor missing shared data / failed to start 40 times
Eb9Airflow lower than demanded
EC1Communication error with the outdoor unit
Ed0No shared data on the network
Ed1Invalid shared data
Ed4Shared data rejected by the control
RDS 2 flashesControl board internal fault (leak detection board)
RDS 3 flashesR32 sensor communication fault
RDS 4 flashesR32 sensor internal fault
RDS fast flashR-32 leak alarm (or system verification test)
RDS steady onDelay mode after leak alarm or fault

Goodman Furnace error codes

CodeMeaning
E10Grounding fault / poor neutral connection
E11Flame rollout switch open
EE0Lockout - too many ignition retries (3)
EE1Pressure switch closed at start of heating cycle
EE2Pressure switch did not close (inducer runs, no ignition)
EE3High (primary) limit open
EE4Flame sensed with no call for heat
EE5Open fuse (short in low voltage wiring)
EE6Low flame signal
EE8High-stage pressure switch closed at start of heating cycle
EE9High-stage pressure switch did not close
EEAReversed line polarity or grounding error
EEbExternal gas valve error - valve not energized when it should be
EECInternal gas valve error - valve energized when it should not be
EEEInternal control fault (IRQ loss)
EEHTwinning error
EEJInducer relay error
EELIgniter relay / igniter circuit fault
EEnIgniter open

Goodman Heat Pump error codes

CodeMeaning
01Low side fault or low pressure switch trip
02High side fault or high pressure switch trip
03Short cycling
04Locked rotor
05Open circuit - compressor off over 4 hours
06Open start circuit
07Open run circuit
08No line voltage
09Low 24 V control voltage
A2Outdoor air temperature sensor fault
A3Outdoor coil temperature sensor fault
b0Indoor blower not running when it should be
b9Indoor airflow lower than requested
CoreSense 1Yellow 1 flash - long run time (low side)
CoreSense 2Pressure trip - yellow 2 flashes (red 2 = lockout)
CoreSense 3Short cycling / pressure switch cycling - yellow 3 (red 3 = lockout)
CoreSense 4Locked rotor - yellow 4 (red 4 = lockout)
CoreSense 5Moderate run trip - yellow 5 (red 5 = lockout)
CoreSense 9Red 9 flashes - PROT output overcurrent
CoreSense solid redSolid red TRIP - call present but compressor not running
d0No shared data on the network
d1Invalid shared data on the network
d2System mismatch - indoor unit cannot supply required airflow
d3Configuration mismatch - shared data does not match hardware
d4Shared data from the loader rejected
E5Outdoor control low-voltage fuse open
EEOutdoor control fault - compressor relay contacts welded
H8High line voltage
L1Lockout - low pressure switch tripped 3 times
L2Lockout - high pressure switch tripped 3 times
L6Lockout - open start circuit detected 4 times
L7Lockout - open run circuit detected 4 times
L8Low line voltage
P0Compressor protector open
Yellow 1 flashLow side fault / low pressure trip / low pressure lockout (older ComfortNet board)
Yellow 2 flashesHigh side fault / high pressure trip / high pressure lockout (older ComfortNet board)
Yellow 3 flashesShort cycling (older ComfortNet board)
Yellow 4 flashesLocked rotor (older ComfortNet board)
Yellow 5 flashesOpen circuit (older ComfortNet board)
Yellow 6 flashesOpen start circuit / lockout (older ComfortNet board)
Yellow 7 flashesOpen run circuit / lockout (older ComfortNet board)
Yellow 8 flashesLow or high line voltage (older ComfortNet board)
Yellow 9 flashesLow 24 V control voltage (older ComfortNet board)
Yellow ON + Red ONCompressor protector open (older ComfortNet board)

Find codes by Goodman model

Goodman/Amana GM9C96/AM9C96

AC9C96AM9C96AM9C960303ANGC9C96GM9C96GM9C960303AN

Goodman/Amana GM9S80/AM9S80

AC9S800403ANAC9S800603ANAC9S800804BNAC9S800805CNAC9S801005CNAM9S800403ANAM9S800603ANAM9S800603BNAM9S800604BNAM9S800803BNAM9S800804BNAM9S800804CNAM9S800805CNAM9S801005CNAM9S801205DNGC9S800403ANGC9S800603ANGC9S800804BNGC9S800805CNGC9S801005CNGM9S800403ANGM9S800603ANGM9S800603BNGM9S800604BNGM9S800803BNGM9S800804BNGM9S800804CNGM9S800805CNGM9S801005CNGM9S801205DN

Goodman/Amana GM9S96/AM9S96

AC9S960403BNAC9S960603BNAC9S960804CNAC9S961005CNAC9S961205CNAC9S961205DNAM9S920403ANAM9S920603BNAM9S920803BNAM9S920804CNAM9S920805CNAM9S921004CNAM9S921005CNAM9S921205DNAM9S960403ANAM9S960603BNAM9S960803BNAM9S960804CNAM9S960805CNAM9S961004CNAM9S961005CNAM9S961205DNGC9S960403BNGC9S960603BNGC9S960804CNGC9S961005CNGC9S961205CNGC9S961205DNGM9S920403ANGM9S920603BNGM9S920803BNGM9S920804CNGM9S920805CNGM9S921004CNGM9S921005CNGM9S921205DNGM9S960403ANGM9S960603BNGM9S960803BNGM9S960804CNGM9S960805CNGM9S961004CNGM9S961005CNGM9S961205DN

Goodman/Amana R-32 AMST/AWSF/ACSF air handlers

ACSF****13**AAAMST***U1300AAAWSF****13**AAAWST****13**AA

Goodman/Amana R-32 GLXS/ALXS

ALXS3BN**10AAALXS4BA**10AAALXS4NA**10AAALXS5BA**10AAGLXS3BN**10AAGLXS4BA**10AAGLXS4MA**10AAGLXS5BA**10AA

Goodman/Amana R-32 GLZS/ALZS

ALZS4BA**10AAALZS4NA**10AAALZS5BA**10AAGLZS4BA**10AAGLZS4MA**10AAGLZS5BA**10AA

Goodman/Amana R-410A GSX/ASX/DSX (ANX/SSX/VSX)

ANX130181ANX130241ANX130301ANX130361ANX130421ANX130481ANX130601ANX130611ANX140181ANX140191ANX140241ANX140251ANX140301ANX140361ANX140371ANX140421ANX140431ANX140481ANX140601ASX180**1ABASX130181ASX130241ASX130301ASX130361ASX130421ASX130481ASX130601ASX130611ASX140181ASX140191ASX140241ASX140251ASX140301ASX140311ASX140361ASX140371ASX140421ASX140431ASX140481ASX140601ASX160181ASX160241ASX160301ASX160311ASX160361ASX160371ASX160421ASX160481ASX160601ASX160611ASXH5***10DSX160241DSX160361GSX16A181GSX16A241GSX16A301GSX16A361GSX16A421GSX16A481GSX16A601GSX16S181GSX16S241GSX16S301GSX16S361GSX16S421GSX16S481GSX110903GSX110904GSX111203GSX111204GSX130181GSX130241GSX130301GSX130361GSX130363GSX130371GSX130421GSX130481GSX130483GSX130484GSX130601GSX130603GSX130604GSX130611GSX140181GSX140191GSX140241GSX140251GSX140301GSX140311GSX140361GSX140371GSX140421GSX140431GSX140481GSX140601GSX160181GSX160241GSX160301GSX160311GSX160361GSX160371GSX160421GSX160481GSX160601GSX160611GSXH5***10SSX140181SSX140241SSX140301SSX140361SSX140421SSX140481SSX140601SSX160241SSX160301SSX160361SSX160421SSX160481SSX160591SSX160601VSX130181VSX130241VSX130301VSX130361VSX130371VSX130421VSX130481VSX130601VSX130611VSX140181VSX140191VSX140241VSX140251VSX140301VSX140311VSX140361VSX140371VSX140421VSX140431VSX140481VSX140601

Goodman/Amana R-410A GSZ/ASZ/DSZ (ANZ/SSZ/VSZ)

ANZ130181ANZ130241ANZ130301ANZ130361ANZ130421ANZ130481ANZ130601ANZ140181ANZ140241ANZ140301ANZ140361ANZ140421ANZ140481ANZ140491ANZ140601ASZ130181ASZ130241ASZ130301ASZ130361ASZ130421ASZ130481ASZ130601ASZ140181ASZ140241ASZ140301ASZ140361ASZ140381ASZ140421ASZ140481ASZ140491ASZ140601ASZ160181ASZ160241ASZ160301ASZ160361ASZ160421ASZ160481ASZ160601ASZ180361ASZ180481ASZ180601ASZH5***10DSZ160241DSZ160361DSZ160481DSZ160601DSZ180361DSZ180481DSZ180601GSZ110903GSZ110904GSZ111203GSZ111204GSZ130181GSZ130191GSZ130241GSZ130251GSZ130301GSZ130311GSZ130361GSZ130363GSZ130371GSZ130421GSZ130481GSZ130483GSZ130484GSZ130601GSZ140181GSZ140241GSZ140301GSZ140361GSZ140371GSZ140421GSZ140481GSZ140491GSZ140601GSZ160181GSZ160241GSZ160301GSZ160361GSZ160421GSZ160481GSZ160601GSZH5***10SSZ140181SSZ140191SSZ140241SSZ140251SSZ140301SSZ140311SSZ140361SSZ140371SSZ140381SSZ140421SSZ140481SSZ140601SSZ160241SSZ160361SSZ160421SSZ160481SSZ160601VSZ130181VSZ130241VSZ130301VSZ130361VSZ130421VSZ130481VSZ130601VSZ140181VSZ140241VSZ140301VSZ140361VSZ140421VSZ140481VSZ140491VSZ140601

Goodman/Amana ComfortNet ASXC/GSXC/DSXC

ASXC160241ASXC160361ASXC160481ASXC160601ASXC180241ASXC180361ASXC180481ASXC180601DSXC160241DSXC160361DSXC160481DSXC160601DSXC180361DSXC180481DSXC180601GSXC160241GSXC160361GSXC160481GSXC160601GSXC180241GSXC180361GSXC180481GSXC180601

Goodman/Amana ComfortNet ASZC/GSZC/DSZC

ASZC160241ASZC160361ASZC160421ASZC160481ASZC160601ASZC180241ASZC180361ASZC180481ASZC180601DSZC160241DSZC160361DSZC160481DSZC160601DSZC180361DSZC180481DSZC180601GSZC160241GSZC160361GSZC160481GSZC160601GSZC180241GSZC180361GSZC180481GSZC180601

Goodman/Amana ComfortBridge AVPTC/MBVC

AVPTC25B14AVPTC29B14AVPTC31C14AVPTC31C14ADAVPTC33C14AVPTC35B14AVPTC37B14AVPTC37C14AVPTC37D14AVPTC39C14AVPTC49C14AVPTC49D14AVPTC59C14AVPTC59D14AVPTC61D14AVPTC183014AVPTC313714AVPTC426014MBVC1201MBVC1601MBVC2001

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.