Updated · by Aurora Star Tech Inc.

Daikin error code L4 on a mini-split means: Radiation fin temperature rise. It is also called Daikin diagnostic code L4.

High severityMini-SplitDaikin FTX-W

Homeowner? What Daikin code L4 means for you

Call a technician Your ductless mini-split is reporting: Radiation fin temperature rise. The ductless mini-split has locked out or cannot run properly. One reset is fine; if the code comes back, it needs a licensed technician to find the cause.

Safe things you can check yourself

  • Check the remote: fresh batteries and the right mode (Cool, Heat or Auto).
  • Check the breaker and the outdoor disconnect; both should be ON.
  • Open the front cover of the indoor unit and rinse the washable filters if they are dusty; let them dry before putting them back.
  • Keep the outdoor unit clear of snow, ice and leaves.
  • Try one reset: turn the power off for 30 seconds, then back on. If the code comes back, stop resetting and call a technician.

Call (647) 657-2977Book a service call

Licensed technicians serving Vaughan, Toronto and the GTA.

What does Daikin error code L4 mean?

With the compressor on, fin temperature is above 82 C (179.6 F). Clears below 77 C (170.6 F). Repeats lead to shutdown. Resets after about 60 minutes of error-free running.

Applies to: FTX30/36WVJU9 with RX30/36WMVJU9 or RK30/36WMVJU9

Common causes of Daikin code L4

  • Faulty outdoor fan motor
  • Blocked airflow
  • Faulty fin thermistor

A technician checks these and 3 other possible causes on site before replacing any part.

Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

Daikin models that use code L4

FTX30WVJU9FTX36WVJU9RK30WMVJU9RK36WMVJU9RX30WMVJU9RX36WMVJU9

Other Daikin Mini-Split codes

CodeMeaning
H6Compressor position sensor abnormality (start failure)
H8Current transformer (CT) abnormality
H9Outdoor air thermistor fault
J3Discharge pipe thermistor fault
J6Outdoor coil thermistor fault
L3Electrical box temperature rise
L5Output overcurrent
P4Radiation fin thermistor fault
U0Refrigerant shortage
U2Low or high supply voltage detected
U4Indoor to outdoor signal error
U7Outdoor PCB internal communication error

All Daikin Mini-Split error codes →

Daikin code L4: homeowner questions

What does Daikin code L4 mean?

Radiation fin temperature rise. With the compressor on, fin temperature is above 82 C (179.6 F). Clears below 77 C (170.6 F). Repeats lead to shutdown. Resets after about 60 minutes of error-free running.

Is it safe to keep using my ductless mini-split with code L4?

It depends on the cause. The ductless mini-split has locked out or cannot run properly. One reset is fine; if the code comes back, it needs a licensed technician to find the cause.

Can I reset Daikin code L4 myself?

You can try one reset (power off for 30 seconds, then on). If Daikin code L4 comes back, the cause is still there and a licensed technician should check it.

Who can fix Daikin code L4 near me?

Aurora Star Tech Inc. repairs Daikin ductless mini-splits in Vaughan, Toronto and across the GTA. Call (647) 657-2977 or book a service call online.

Homeowner help: AC Running But Not Cooling: What to Check · Heat Pump Not Heating or Blowing Cold Air

Troubleshooting guides

Source: Daikin FTX-W service manual SiUS042228E, Troubleshooting 4.25, p.106. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.